TESTBOY TV 450
Technical specification
63
I
Δ
N × 1/2
I
Δ
N × 1
I
Δ
N × 2
I
Δ
N × 5
RCD I
Δ
I
Δ
N (mA) AC A B* AC A
B* AC A B
AC
A
B* AC
A
B*
10
5 3.5
5 10 20 20 20 40 40
50 100
100
9
9 9
30
15
10.5
15 30 42 60 60 84 120 150 212
300
9
9 9
100
50 35 50 100 141 200 200 282 400 500 707
1000
9
9 9
300
150
105 150 300 424 600 600 848 n.a. 1500 n.a.
n.a.
9
9 9
500
250 175 250 500 707 1000 1000 1410 n.a. 2500 n.a. n.a.
9
9 9
1000
500
350 500 1000
1410
n.a. 2000
n.a. n.a. n.a. n.a.
n.a.
9
9
n.a.
n.a......................................................not applicable
AC type..............................................sine wave test current
A type…… .........................................pulsed current
B type ................................................smooth DC current
9.3.2 Contact voltage RCD-Uc
Measuring range according to EN61557 is 20.0 V
÷
31.0V for limit contact voltage 25V
Measuring range according to EN61557 is 20.0 V
÷
62.0V for limit contact voltage 50V
Measuring range (V)
Resolution (V)
Accuracy
0.0
÷
19.9
0.1
(-0 % / +15 %) of reading ± 10 digits
20.0
÷
99.9
(-0 % / +15 %) of reading
The accuracy is valid if mains voltage is stabile during the measurement and PE
terminal is free of interfering voltages.
Test current ...................................... max. 0.5
×
I
Δ
N
Limit contact voltage ......................... 25 V, 50 V
Specified accuracy is valid for complete operating range.
9.3.3 Trip-out time
Complete measurement range corresponds to EN 61557 requirements.
Maximum measuring times set according to selected reference for RCD testing.
Measuring range (ms)
Resolution (ms)
Accuracy
0.0
÷
40.0
0.1
±
1 ms
0.0
÷
max. time *
0.1
±
3 ms
* For max. time see normative references in
4.2.5
– this specification applies to max.
time >40 ms.
Test current ...................................... ½
×
I
Δ
N
, I
Δ
N
, 2
×
I
Δ
N
, 5
×
I
Δ
N
5
×
I
Δ
N
is not available for I
Δ
N
=1000 mA (RCD type AC) or I
Δ
N
≥
300 mA (RCD types A,
B*).
2
×
I
Δ
N
is not available for I
Δ
N
=1000 mA (RCD type A) or I
Δ
N
≥
300 mA (RCD type B*).
1
×
I
Δ
N
is not available for I
Δ
N
=1000 mA (RCD type B)*.
Specified accuracy is valid for complete operating range.
9.3.4 Trip-out current
Trip-out current
Complete measurement range corresponds to EN 61557 requirements.
Measuring range I
Δ
Resolution
I
Δ
Accuracy
0.2
×
I
Δ
N
÷
1.1
×
I
Δ
N
(AC type)
0.05
×
I
Δ
N
±
0.1
×
I
Δ
N
0.2
×
I
Δ
N
÷
1.5
×
I
Δ
N
(A type, I
Δ
N
≥
30 mA)
0.05
×
I
Δ
N
±
0.1
×
I
Δ
N