TESTBOY TV 450
Warnings and notes
8
Warnings related to measurement functions:
Insulation resistance
Insulation resistance measurement should only be performed on de-energized
objects!
Do not touch the test object during the measurement or before it is fully
discharged! Risk of electric shock!
When an insulation resistance measurement has been performed on a capacitive
object, automatic discharge may not be done immediately! The warning message
and the actual voltage is displayed during discharge until voltage drops below
10 V.
Do not connect test terminals to external voltage higher than 600 V (AC or DC) in
order not to damage the test instrument!
Continuity functions
Continuity measurements should only be performed on de-energized objects!
Parallel impedances or transient currents may influence test results.
Testing PE terminal
If phase voltage is detected on the tested PE terminal, stop all measurements
immediately and ensure the cause of the fault is eliminated before proceeding
with any activity!
Notes related to measurement functions:
General
The indicator means that the selected measurement cannot be performed
because of irregular conditions on input terminals.
Insulation resistance, continuity functions and earth resistance measurements
(TESTBOY TV 450 (TYPE B)) can only be performed on de-energized objects.
PASS / FAIL indication is enabled when limit is set. Apply appropriate limit value
for evaluation of measurement results.
In the case that only two of the three wires are connected to the electrical
installation under test, only voltage indication between these two wires is valid.
Insulation resistance
If voltages of higher than 10 V (AC or DC) is detected between test terminals, the
insulation resistance measurement will not be performed. If voltages of higher
than 10 V (AC or DC) is detected between test terminals, the insulation
resistance measurement will not be performed.
The instrument automatically discharge tested object after finished
measurement.
A double click of TEST key starts a continuous measurement.
Содержание TV 450
Страница 1: ...TESTBOY TV 450 TESTBOY TV 450 Type B Instruction manual Version 1 5 Code no 20 751 769...
Страница 75: ...TESTBOY TV 450 Appendix C 75...
Страница 76: ...TESTBOY TV 450 Appendix C 76...