TESTBOY TV 450
Earth resistance
48
Figure 5.31: Resistance to earth, measurement of a lighting protection system
Earth resistance measurements, common measurement procedure
Select
EARTH
function using the function selector switch.
Enable and set
limit
value(optional).
Connect
test leads to the instrument
Connect
the item to be tested (see figures 5.30, 5.31).
Press the
TEST
key to perform the measurement..
Store
the result by pressing the MEM key (optional).
Figure 5.32: Example of earth resistance measurement result
Displayed results for earth resistance measurement:
R..............Earth resistance,
Rp............Resistance of S (potential) probe,
Rc............Resistance of H (current) probe.
Notes
:
High resistance of S and H probes could influence the measurement results. In
this case, “Rp” and “Rc” warnings are displayed. There is no pass / fail indication
in this case.
High noise currents and voltages in earth could influence the measurement
results. The tester displays the “noise” warning in this case.
Probes must be placed at sufficient distance from the measured object.
Содержание TV 450
Страница 1: ...TESTBOY TV 450 TESTBOY TV 450 Type B Instruction manual Version 1 5 Code no 20 751 769...
Страница 75: ...TESTBOY TV 450 Appendix C 75...
Страница 76: ...TESTBOY TV 450 Appendix C 76...