TESTBOY TV 450
Testing RCD
36
5.4 Testing RCDs
Various test and measurements are required for verification of RCD(s) in RCD protected
installations. Measurements are based on the EN 61557-6 standard.
The following measurements and tests (sub-functions) can be performed:
Contact voltage,
Trip-out time,
Trip-out current,
RCD autotest.
See chapter
4.1 Function selection
for instructions on
key functionality.
Figure 5.16: RCD test
Test parameters for RCD test and measurement
TEST RCD
sub-function
test [RCDt, RCD I, AUTO, Uc].
I
Δ
N
Rated
RCD residual current sensitivity I
Δ
N
[10 mA, 30 mA, 100 mA, 300 mA,
500 mA, 1000 mA].
type
RCD
type
[ , ]
,
test current
waveform
plus
starting
polarity
[
,
,
,
,
*,
*]
.
MUL
Multiplication
factor for test current [½, 1, 2, 5 I
Δ
N
].
Ulim Conventional
touch
voltage
limit
[25 V, 50 V].
* Model TESTBOY TV 450 (TYPE B)
Notes
:
Ulim can be selected in the Uc sub-function only.
The instrument is intended for testing of
G
eneral (non-delayed) and
S
elective (time-
delayed) RCDs, which are suited for:
Alternating residual current (AC type, marked with
symbol),
Pulsating residual current (A type, marked with symbol).
Pulsating residual current (A type, marked with symbol).
Model TESTBOY TV 450 (Type B): DC residual current (B type, marked with
symbol).
Time delayed RCDs have delayed response characteristics. As the contact voltage pre-
test or other RCD tests influence the time delayed RCD it takes a certain period to
recover into normal state. Therefore a time delay of 30 s is inserted before performing
trip-out test by default.