7
3.4 Connections
Attention! Do NOT connect the metallic parts of the antenna connector or the device
’s
terminals directly or indirectly to the protective ground, because this may damage the
device!
3.4.1 Wiring diagrams according to output control modes
System terminal inputs and outputs:
V+
Supply voltage
12…30V AC/DC (min. 500mA)
V-
Supply voltage negative (if DC)
IN1
Dry contact input 1
IN2
Dry contact input 2
IN3
Dry contact input 3
IN4
Dry contact input 4
OUT1
Relay output 1 (normally open dry contact, max. 1A@24V AC/DC)
OUT2
Relay output 2 (normally open dry contact, max. 1A@24V AC/DC)
Control mode 1:
- For one or two gates, or one gate with
two
opening
options
(partial/total
opening).
- Both outputs are normally open (NO).
- OUT1 is controlled by call with caller
identification.
- OUT2 is controlled by calls from private
(hidden) number.
- A control call only opens the gate.
Closing should be done automatically by
the gate automation control board.
Control mode 2:
- For one or two gates or one gate with
two
opening
options
(partial/total
opening).
- Both outputs are normally open (NO).
- Both outputs are controlled by call with caller identification as configured (OUT1 only, OUT2
only, or both at the same time).
- Output control permission can be configured separately for each user and each output.
- A control call only opens the gate. Closing should be done automatically by the gate
automation control board.