Programming Manual
–
T3AWG3K-C Series Arbitrary Waveform Generator
True-Arb Operating Mode
37
Important Note:
there is only one sequence defined for an instrument. For each entry of the
sequencer the number of repetitions and waveform's length are common to all channels,
while Amplitude/Offset (Voltage High/Low) and waveform’ shape are independent o
f each
other.
Use the following sequence commands to define and edit a sequence:
Command
Description
SEQuence:ELEM[n]:AMPlitude[m]
Sets or returns peak to peak
voltage level for sequence
element n of channel m.
SEQuence:ELEM[n]:OFFset[m]
Sets or returns the offset for
sequence
element
n
of
channel m.
SEQuence:ELEM[n]:VOLTage:HIGH[m]
Sets or returns the maximum
level
of
the
waveform
expressed in Volts for sequence
element n of channel m.
SEQuence:ELEM[n]:VOLTage:LOW[m]
Sets or returns the minimum
level
of
the
waveform
expressed in Volts for sequence
element n of channel m.
SEQuence:ELEM[n]:LENGth
Sets or returns the number of
waveform
samples
for
sequence element n.
SEQuence:ELEM[n]:LOOP:COUNt
Sets or returns the number of
repetitions
for
sequence
element n.
SEQuence:ELEM[n]:WAVeform[m]
Sets or returns the waveform
(among those in the waveforms
list) to be assigned to the
sequence
element
n
of
channel m.
SEQuence:LENgth
Sets or returns the number of
elements in the sequencer.
SEQuence:NEW
Creates a new sequence.
SEQuence:FOCus
Sets which sequence element is
shown on the display.
SEQuence:ELEM[n]:WAITEvent
Sets or returns the wait event
type for sequence element n.