10
3.2 Deactivation of wireless safety system
Procedure only with hold to run commands.
Warning:
The safety devices are excluded!
ACTIVATION
Press together
P1
and
P2
and keep them pressed
for 3s. The buzzer makes one beep.
P2
P1
keep
pressed
+
3 s
Open the door (in
hold-to-run
mode) in order
to set up the upper limit switch.
Close the door (in
hold-to-run
mode) in order
to set up the down limit switch.
hold-to-run
HOLD TO
RUN
L4 FLASH F
AST
hold-to-run
DEACTIVATION
Press together
P1
and
P2
and keep them pressed for
3s or wait
time out time
of 90s from the last button
pression. The buzzer makes one beep.
P2
P1
keep
pressed
+
3 s
ON
1 2 3
ON
1 2 3
ON
This function is possible ONLY within 30 seconds from the power on of the control unit.
By default DIP1 is ON (system activated).
• Switch the unit on and move DIP1 to OFF within 30 seconds.
ON
to
OFF
The control unit will emit
6
beeps
if the system has been correctly deactivated.
It is possible activate the safety system again, moving DIP1 from OFF to ON within 30 seconds from
power-on. After keeping pressed P1 button for 5 seconds, the control unit will emit
7
beeps
.
• Press P1 button for 5 seconds and hold it down
3.1 Limit switches configuration Factory setting: ACTIVATED