Alarm Reset: The alarm condition is cleared, allowing the alarm to trigger again based on
input.
•
Acknowledge: The input must cross the reset point to trigger new alarm after it has been
acknowledged.
6.40
Modbus
Functionality
•
The Tek-LCD 7801C supports Modbus RTU, Modbus ASCII, Enron Modbus, and Ethernet Modbus
TCP/IP. The Server mode is a standard Tek
-LCD 7801C feature; it responds to requests and
accepts writes from a Modbus client.
•
The Client mode can request process variables from server devices; the input variables can be
scaled, combined with other variables using math functions, and they can be written to other
server devices using the Modbus output functions.
•
The Snooper mode can listen and read the process variables being transmitted on the RS-485
bus without causing any disruptions to the network.
•
The Spoofer Modbus output is used to replace Modbus devices that have been removed from
the network; there is no need to make changes to the Modbus client’s configuration.
6.41
Setup Modbus Inputs (Server)
The Modbus Server mode is a standard feature. The controller can accept up to 199 Modbus inputs
sent by a Modbus Client. The inputs can be used as the source for channels, math functions, alarms,
relay control, etc.
•
Enter Modbus Input tag
•
Type: Select the data type The register number is displayed to the right
•
Decimals: Number of decimals
•
Units: Select units or enter custom unit
•
Break: Value or condition for comm. break
•
Timeout: Select timeout to detect break
•
Input Action: Select action when new value is received (e.g. Add to Total 1 the value
written)