23
4.2.7
Analog Output Connections
•
Figure 13
shows
examples for isolated 4
-20 mA transmitter output connections.
Terminal connectors are labelled individually.
•
The analog outputs are isolated from each other and from the inputs. They are powered
internally to provide an active 4-20 mA output loop. The outputs can be powered
externally by connecting the positive voltage to the Ex+ terminal.
Fig 13: Active 4
-20 mA Output Powered by Controller
Fig 14:
Passive 4-
20 mA Output Powered by External Supply
4.2.8
Digital Output Connections
The digital outputs can be used to drive digital inputs, alarm annunciators, or other devices
such as solid-state relays that can be driven with low voltage signals.
Fig 15: Digital Outputs Driving 5 V Solid State Relay
I+ Ex+ I-
mA-
mA+
Analog Output
Remote Display,
Chart Recorder, Etc
Con troll er
I+ Ex+ I-
mA-
mA+
Analog Output
Remote Display,
Chart Recorder, Etc
External
Power Supply
+
-
Digital Outputs
1
2
3
4
G
Alarm
Annunciator
Load
V
AC