The Remote 2 Sensor attached to RTU 1 is being read as an open circuit. RTU 1 will continue operation
using all remaining sensors. If all of the sensors are unavailable, the control will continue to operate
as if RTU 1 was not connected to the control. This error message can be cleared once the sensor has
been repaired. Locate and repair the problem as described in the Data Brochure D 070. To clear the
error message from the control, press either the Menu or Item button. REMOTE 2
≠
NONE
The Remote 3 Sensor attached to RTU 1 is being read as a short circuit. RTU 1 will continue operation
using all remaining sensors. If all of the sensors are unavailable, the control will continue to operate
as if RTU 1 was not connected to the control. This error message can be cleared once the sensor has
been repaired. Locate and repair the problem as described in the Data Brochure D 070. To clear the
error message from the control, press either the Menu or Item button. REMOTE 3
≠
NONE
The Remote 3 Sensor attached to RTU 1 is being read as an open circuit. RTU 1 will continue operation
using all remaining sensors. If all of the sensors are unavailable, the control will continue to operate
as if RTU 1 was not connected to the control. This error message can be cleared once the sensor has
been repaired. Locate and repair the problem as described in the Data Brochure D 070. To clear the
error message from the control, press either the Menu or Item button. REMOTE 3
≠
NONE
Cooling control is selected but there is no display RTU connected to the
tN1 6 terminal. The control
will continue to operate as if COOL MOD was set to NONE. To clear the error message from the control,
press either the Menu or Item button.
Error Displayed
Description of Error
The control is no longer able to read the information that is coming from RTU 1. Reconnect RTU 1 and
press either the Menu or Item button to clear the error. If the RTU has been deliberately disconnected
from the control, remove power from the control for 10 seconds and the repower the control in order
to clear the error message.
The Remote 1 Sensor attached to RTU 1 is being read as a short circuit. RTU 1 will continue operation
using all remaining sensors. If all of the sensors are unavailable, the control will continue to operate
as if RTU 1 was not connected to the control. This error message can be cleared once the sensor has
been repaired. Locate and repair the problem as described in the Data Brochure D 070. To clear the
error message from the control, press either the Menu or Item button. REMOTE 1
≠
NONE.
The Remote 1 Sensor attached to RTU 1 is being read as an open circuit. RTU 1 will continue operation
using all remaining sensors. If all of the sensors are unavailable, the control will continue to operate
as if RTU 1 was not connected to the control. This error message can be cleared once the sensor has
been repaired. Locate and repair the problem as described in the Data Brochure D 070. To clear the
error message from the control, press either the Menu or Item button. REMOTE 1
≠
NONE
The Remote 2 Sensor attached to RTU 1 is being read as a short circuit. RTU 1 will continue operation
using all remaining sensors. If all of the sensors are unavailable, the control will continue to operate
as if RTU 1 was not connected to the control. This error message can be cleared once the sensor has
been repaired. Locate and repair the problem as described in the Data Brochure D 070. To clear the
error message from the control, press either the Menu or Item button. REMOTE 2
≠
NONE
369
Error
Messages (3 of 3)
The error messages listed below for RTU 1 will be the same for RTU 2, RTU 3, RTU 4, RTU 5 and RTU 6.
This warning message will be displayed if the air temperature sensed by RTU 1 exceeds the setting
of the ROOM HOT item in the Monitor menu of RTU 1. The control will continue to operate as normal
with this warning. To clear the warning press either the Menu or Item button.
This warning message will be displayed if the air temperature sensed by RTU 1 is below the setting
of the ROOM HOT item in the Monitor menu of RTU 1. The control will continue to operate as normal
with this warning. To clear the warning press either the Menu or Item button.