Copyright © D 369 -10/00
19 of 32
Actual
Setting
PUMP, VLV, THRM
Default = VLV
Section
LT
D
INST
ADV
Range
Access
Level
Description
Item Field
USER
ONE, TWO
Default = ONE
NONE, CG
Default = CG
NONE, CTRL
Default = NONE
The type of zoning device that is to be used.
(RTU or indoor sensor is present.)
Selects single stage or two stage operation.
(RTU or indoor sensor is present in even zone,
and RTU is not present in the preceding
odd zone.)
Selects if this zone is part of the cooling group.
(RTU or indoor sensor is present; Zone 1 to Zone 5.)
COOL MOD
≠
NONE
Selects if this zone is operated on the control
schedule.
(Non-display RTU or indoor sensor is present.)
DIP switch =
Setback
A1
A2
A3
B1
C
Note:
The Zone Adjust menu is repeated for each zone that an RTU or indoor sensor is connected to. The Zone Adjust menu is indicated
by
Adjust in the left hand side of the display, and Zone followed by the zone number in the bottom of the display.
369
Zone
Adjust
Menu (1 of 2)
0:10 to 3:00 hr
Default = 0:30 hr
NONE, STRT
Default = NONE
0:30 to 4:00 min
Default = 3:00 min
0:10 to 2:00 min
Default = 0:30 min
OFF, 0:10 to 4:00 min
Default = 0:30 min
5:00 to 30:00 min
Default = 15:00 min
30 to 240 hr, OFF
Default = 70 hr
The time the heating zones assigned to the
cooling group must be off before cooling operation
is allowed.
COOL MOD
≠
NONE
Enables or disables the Optimum Start feature
for the cooling system.
COOL MOD = CTRL
The time required for a thermal zone valve to
open.
any ZNi OUTP = THRM (
i = 1, . . ., 6)
The time required for a thermal zone valve to
close.
any ZNi OUTP = THRM (
i = 1, . . ., 6)
The maximum length of time that a zone device
and the system pump continues to operate after
a heat demand is removed.
The cycle length used for heating operation.
The frequency with which the control exercises
the pumps and valves that are operated by
the control.
B1
B3
A1
A1
A1
A1
A1
369
Control
Adjust
Menu (2 of 2)
Section
LT
D
INST
ADV
Range
Access
Level
Description
Item Field
USER
Actual
Setting