background image

Copyright © D 369 -10/00

17 of 32

None

Setback

Misc

Cleaning

The control’s exterior can be cleaned using a damp cloth. Moisten cloth with water and wring out prior to wiping control. Do not use
solvents or cleaning solutions.

DIP Switch Settings

The DIP Switch settings on the control are very important and should be set to the appropriate
settings prior to making any adjustments to the control through the user interface. The DIP switch
settings change the items that are available to be viewed and/or adjusted in the user interface.

LOCK / UNLOCK 

The 

Lock / Unlock DIP switch is used to lock and unlock the access level of the control and tekmar Net ™ tN1 / tN2 device(s). Once

locked, access levels cannot be changed. To determine if the control is currently locked or unlocked, a small segment representing
a padlock is viewed in the bottom right hand corner of the display. When the padlock is closed, the access level cannot be changed.

To change the access level, set the DIP switch to the unlocked or down position. The current access level of the control or 

tekmar

Net™ (tN1/2) device is viewed in its Miscellaneous (Misc) menu. While viewing the access level, use the up and down keys to select
between the Limited (LTD), User (USER), Installer (INST), or Advanced (ADV) access levels.

To lock the access level, select the appropriate access level in the Miscellaneous (Misc) menu and move the DIP switch from the
unlocked position to the locked position. As long as the DIP switch is in the locked position, the access level of the control or tekmar
Net™ (tN1 / tN2) device can no longer be viewed or adjusted in its Miscellaneous (Misc) menu.

SETBACK / NONE 

The 

Setback / None DIP switch enables and disables the setback functions of the control. When the DIP switch is set to the None

or down position, the control ignores any external setback signal, and its user interface does not display the 

Unoccupied adjustments.

When the DIP switch is set to the 

Setback position, the internal clock in the control is enabled. The control also responds to an external

setback signal generated on the 

UnO Sw terminal.

Access Levels

The tekmar Zone Control 369 comes with four Access Level settings. These Access Levels restrict the number of Menus, Items, and
Adjustments that can be accessed by the user. The four access levels are Limited (LTD), User (USER), Installer (INST) and
Advanced (ADV).

The access level of the control is found in the Miscellaneous (Misc)
menu when the 

Lock/Unlock DIP switch is set to the unlocked position.

In the Advanced access level, all of the control settings are available to
the user. In the User access level, only a few of the menus and items
are available. The Limited access level is the most restricted of them all.
The control’s factory setting is Installer (INST). This access level is
sufficient for the normal set up of the control. Once the control is set up,
the appropriate access level should be selected for the people that deal
with the control on a regular basis.

- 01/09

- 01/09

Содержание Zone Control 369

Страница 1: ...om Temperatue Unit RTU Item Menu Input Indoor Sensor 70 Test None Setback off red red Data Brochure Zone Control 369 D 369 01 09 The Zone Control 369 is designed to control the temperature in up to si...

Страница 2: ...Display LCD as the method of supplying information You can use the LCD in order to setup and monitor the operation of your system The 369 has four push buttons Menu Item for selecting and adjusting s...

Страница 3: ...access the zone settings for a particular zone select the Zone Adjust menu for that zone by using the Menu button Adjust will be displayed in the left hand side of the display and Zone followed by th...

Страница 4: ...d Night mode Ovr Cool AM PM sec min hr Zone Displays when a zone is in operation Optimum Stop Displays when a zone is in optimum stop Optimum Start Displays when a zone is in optimum start Override Di...

Страница 5: ...order to prevent short cycling the 369 ensures that the zone relays remain on or off for a minimum amount of time PID Zoning Logic Proportional P Proportional control logic compares the actual zone te...

Страница 6: ...contactisoperatedbasedonthezoningdevice s selected RefertotheZONEOUTPUTsectionforsystem pump operation The system pump is also operated based on the purge and exercise functions EXERCISING EXERCISE Th...

Страница 7: ...e relay on time increases until it reaches the maximum of the cycle length The Hi stage relay is then turned on and its on time is increased as the load increases When the heating load decreases again...

Страница 8: ...ir sensor which is used to control the heating and cooling air temperature while a slab sensor connected to the 063 RTU controls the floor slab temperature During mild conditions the floor slab is mai...

Страница 9: ...e Settings section of this brochure Zone Schedule ZONE The zone schedule allows each zone to have its own independent schedule A zone schedule is only available for zones using display RTUs The ZONE s...

Страница 10: ...occupied or temporary unoccupied override is selected the 369 operates the zone s in the selected override mode for 3 hours from the time the selection is made Once completed the control reverts to t...

Страница 11: ...ther items In cases where a restricted temperature range is required the RTU s range can be limited by changing the access level of the RTU Remote indoor sensors can be connected to the 063 to average...

Страница 12: ...ittings Before removing the knockouts check the wiring diagram and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections as the wires will interfe...

Страница 13: ...m pump circuit to the Sys Pmp terminal 17 and the second side of the pump circuit to the neutral N side of the 115 V ac power supply Zone Pumps and Zone Valves Note The zoning outputs are isolated ter...

Страница 14: ...to the Com and UnO Sw 4 and 1 terminals When these terminals short together the control registers an Unoccupied signal One Stage RTU and Indoor Sensor Connections RTUs and indoor sensors provide indoo...

Страница 15: ...or sensor is used connect the two wires from the sensor to the Com and Indr 4 terminals 24 and 27 Note If an RTU is connected to tN1 4 an indoor sensor can not be connected to Indr 4 Zone 6 tN1 6 or I...

Страница 16: ...erminals 7 and 6 make sure power to the pump or valve circuit is off and install a jumper between the Com 1 2 and Zn 1 terminals 7 and 6 When the zone circuit is powered up the zone pump should turn o...

Страница 17: ...he unlocked position to the locked position As long as the DIP switch is in the locked position the access level of the control or tekmar Net tN1 tN2 device can no longer be viewed or adjusted in its...

Страница 18: ...oom air temperature of zone 6 This is the signal that is being received from a zone control OFF 30 to 110 F OFF 1 to 43 C This is the signal that is being sent to a reset or additional zone control OF...

Страница 19: ...the zone number in the bottom of the display 369 Zone Adjust Menu 1 of 2 0 10 to 3 00 hr Default 0 30 hr NONE STRT Default NONE 0 30 to 4 00 min Default 3 00 min 0 10 to 2 00 min Default 0 30 min OFF...

Страница 20: ...was last cleared The total number of Cooling relay running hours since this item was last cleared The total number of Zn 1 relay running hours since this item was last cleared The total number of Zn 2...

Страница 21: ...r will increase if there is a lowering of the input voltage beyond the control s usable range This item can also be used as an indication of the quality of the power source L T D I N S T A D V Range A...

Страница 22: ...switch Setback C C C C Occ 2 UnOcc 2 to 11 50 PM or to 23 50 Default to 11 50 PM or to 23 50 Default to 11 50 PM or to 23 50 Default Time when the first occupied period begins every day 7DAY 24h 24hr...

Страница 23: ...002 When using display RTUs several items related to the system are no longer available in the control s User Interface These items are available only in the RTU s User Interface Also the number of i...

Страница 24: ...tment in the LTD access level MODE OFF and DIP switch Setback The desired cooled room air temperature during an occupied period Note There is only a 3 F 1 C adjustment in the LTD access level RTU 6 an...

Страница 25: ...is an adjustable item If the air temperature measured by the RTU drops below this setting the control will display a warning message OFF 20 to 80 F OFF 7 to 27 C Default OFF Note To clear the recorded...

Страница 26: ...le refer to the Example given in the Schedule menu of the 369 Note To skip an event during a schedule select the Null event Use the arrow keys to select the Time between 11 50 PM and 12 00 AM is displ...

Страница 27: ...utes while the test sequence is paused the control exits the entire test routine If the test sequence is paused the Test button can be pressed again to advance to the next step This can also be used t...

Страница 28: ...tch the piping of the system This is a relatively simple step that tends to be overlooked however it can often save hours of time troubleshooting a system Note flow directions in the system paying clo...

Страница 29: ...te Access level must be ADV in order to clear the error The control was unable to read a piece of information stored in the Miscellaneous Menu Because of this the control was required to load the fact...

Страница 30: ...nu Because of this the control was required to load the factory settings into all of the items in the Adjust menu The control will stop operation until all of the items available in the Adjust menu of...

Страница 31: ...o clear the error message The Remote 1 Sensor attached to RTU 1 is being read as a short circuit RTU 1 will continue operation using all remaining sensors If all of the sensors are unavailable the con...

Страница 32: ...The purchaser by taking receipt of the tekmar product product acknowledges receipt of the terms of the warranty and acknowledges that it has read and understands same tekmar warrants each tekmar prod...

Отзывы: