An incorrect device has been connected to the
tekmar Net™ tN1 1 input terminal. Once the problem
has been corrected, press either the Menu or Item button to clear the error message from the control.
A short circuit has been read between the
tN1 1 terminal and a Com terminal on the control. Either the
wires leading to the RTU device are shorted or the polarity of the wires are reversed. Determine the
cause and remove the short. To clear this error, press either the Menu or Item button.
The control is no longer able to read the information that is coming from RTU 1. Reconnect the RTU
and press either the Menu or Item button to clear the error. If the RTU has been deliberately disconnected
from the control, remove power from the control for 10 seconds and then repower the control in order
to clear the error message.
The control is no longer able to read the outdoor sensor due to a short circuit. In this case the control
assumes an outdoor temperature of 32
°
F (0
°
C) and continues operation. Locate and repair the problem
as described in the Data Brochure D070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
The control is no longer able to read the outdoor sensor due to an open circuit. In this case the control
assumes an outdoor temperature of 32
°
F (0
°
C) and continues operation. Locate and repair the problem
as described in the Data Brochure D070. To clear the error message from the control after the sensor
has been repaired, press either the Menu or Item button.
RTU 1 was unable to store a piece of information into its EEPROM. This error can be caused by a
noisy power source. The control will display the error message and will continue to operate as normal.
Pressing either the Menu or Item button will clear this error.
RTU 1 was unable to read a piece of information stored in the Adjust Menu. Because of this, the control
was required to load the factory settings into all of the items in the Adjust menu. The control will stop
operation until all of the items available in the Adjust menu of the control have been checked by the
user or installer.
Note:
Access level must be ADV in order to clear the error.
RTU 1 was unable to read a piece of information stored in the Monitor Menu. Because of this, the
control was required to load the factory settings into all of the items in the Monitor menu. The control
will continue to display the error message until all of the items available in the Monitor menu of the
control have been checked by the user or installer.
Note:
Access level must be ADV in order to clear the error.
RTU 1 was unable to read a piece of information stored in the Schedule Menu. Because of this, the
control was required to load the factory settings into all of the items in the Schedule menu. The control
will continue to display the error message until all of the items available in the Schedule menu of the
control have been checked by the user or installer.
Note:
Access level must be ADV in order to clear the error.
RTU 1 was unable to read a piece of information stored in the Miscellaneous Menu. Because of this,
the control was required to load the factory settings into all of the items in the Miscellaneous menu.
The control will continue to display the error message until all of the items available in the Miscellaneous
menu of the control have been checked by the user or installer.
Note:
Access level must be ADV in order to clear the error.
The error messages listed below for RTU 1 will be the same for RTU 2, RTU 3, RTU 4, RTU 5 and RTU 6.
369
Error
Messages (2 of 3)
The error messages listed below for 1 tN1 will be the same for 2 tN1, 3 tN1, 4 tN1, 5 tN1 and 6 tN1.
A short circuit has been read between the
tN1 1 terminal and a Com terminal on the control. Either the
wires leading to the RTU device are shorted or the polarity of the wires are reversed. Determine the
cause and remove the short. To clear this error, press either the Menu or Item button.