ZONE CONTROL OPERATION WITH A TEKMAR OUTDOOR RESET CONTROL 

The 369 can provide indoor temperature feedback to a tekmar Reset Control. When multiple Zone Controls are used, each zone
control uses its 

Zo Out output to sequentially pass the information to the tekmar Reset Control. The ZO OUT item displayed in the

view menu represents the target from the zone with the highest heat requirement. The tekmar Reset Control uses this target to
determine the water temperature required to satisfy the zone with the highest heat requirement.

ZONE OUTPUT (ZN OUTP) 

The ZN OUTP adjustment in the Zone Adjust menu of the control selects the zoning
device used for each zone, and affects the operation of the system pump.

When PUMP is selected, the control assumes the device used to control the heat
delivery is a pump. When the zone turns on, the control does not operate the system
pump.

When VLV is selected, the control assumes the device used to control the heat delivery
is a fast acting spring return valve. When the zone turns on, the control turns on the
system pump.

When THRM is selected, the control assumes the device used to control the heat delivery is a slow acting zone valve with a
thermal actuating motor. When the zone turns on, the system pump is held off for a period of time to allow the thermal motor zone
valve to fully open. This time is adjustable through the thermal open (THRM OPEN) setting in the Control Adjust menu of the
control. The thermal close (THRM CLS) setting in the Control Adjust menu of the control sets the time required for the thermal
motor zone valve to close.

SYSTEM PUMP OPERATION 

The system pump (

Sys Pmp) contact is operated based on the zoning device(s) selected. Refer to the ZONE OUTPUT section for system

pump operation. The system pump is also operated based on the purge and exercise functions.

EXERCISING (EXERCISE) 

The 369 has a built-in exercising function. The exercising period is adjustable and comes factory set at 70 hours. If the zoning devices
or the system pump has not been operated at least once during every exercising period, the control turns on the output for 10 seconds.
This minimizes the possibility of a pump or valve seizing during a long period of inactivity. The Test LED flashes anytime the control
is exercising.

Note: 

The zone relay exercising time is increased to the THRM OPEN setting if THRM is selected as the zoning device.

PURGING (PURGE) 

The 369 includes a purging function which allows for any excess heat available in the boiler to be purged into the zones. The 369 removes
the call for heat from the reset control some time before the zones are turned off. The purging time is adjustable based on the PURGE
setting in the Control Adjust menu of the control.

Section A2: One Stage Heating

ONE STAGE HEATING 

A one stage heating zone has one RTU or indoor sensor controlling a
single heating terminal. One RTU or indoor sensor therefore controls
one output relay. If an RTU is used to control a one stage heating zone,
the RTU must be connected to a 

tN1 terminal. If an RTU is connected

to an even numbered 

tN1 terminal (i.e. tN1 2, tN1 4 or tN1 6), ONE must

be selected through the STG NUM adjustment in the Zone Adjust menu
of the control. If an indoor sensor is used to control a one stage heating
zone, the sensor can only be connected to an 

Indr terminal (i.e. Indr 2,

Indr 4 or Indr 6), and ONE must be selected through the STG NUM
adjustment in the Zone Adjust menu of the control.

Example: 

An RTU connected between 

Com and

tN1 1 terminals (20 and 21) is used to control the
output relay 

Zn 1, and an RTU connected between

Com and tN1 2 terminals (20 and 22) is used to
control the output relay 

Zn 2.

- 01/09

- 01/09

Содержание Zone Control 369

Страница 1: ...om Temperatue Unit RTU Item Menu Input Indoor Sensor 70 Test None Setback off red red Data Brochure Zone Control 369 D 369 01 09 The Zone Control 369 is designed to control the temperature in up to si...

Страница 2: ...Display LCD as the method of supplying information You can use the LCD in order to setup and monitor the operation of your system The 369 has four push buttons Menu Item for selecting and adjusting s...

Страница 3: ...access the zone settings for a particular zone select the Zone Adjust menu for that zone by using the Menu button Adjust will be displayed in the left hand side of the display and Zone followed by th...

Страница 4: ...d Night mode Ovr Cool AM PM sec min hr Zone Displays when a zone is in operation Optimum Stop Displays when a zone is in optimum stop Optimum Start Displays when a zone is in optimum start Override Di...

Страница 5: ...order to prevent short cycling the 369 ensures that the zone relays remain on or off for a minimum amount of time PID Zoning Logic Proportional P Proportional control logic compares the actual zone te...

Страница 6: ...contactisoperatedbasedonthezoningdevice s selected RefertotheZONEOUTPUTsectionforsystem pump operation The system pump is also operated based on the purge and exercise functions EXERCISING EXERCISE Th...

Страница 7: ...e relay on time increases until it reaches the maximum of the cycle length The Hi stage relay is then turned on and its on time is increased as the load increases When the heating load decreases again...

Страница 8: ...ir sensor which is used to control the heating and cooling air temperature while a slab sensor connected to the 063 RTU controls the floor slab temperature During mild conditions the floor slab is mai...

Страница 9: ...e Settings section of this brochure Zone Schedule ZONE The zone schedule allows each zone to have its own independent schedule A zone schedule is only available for zones using display RTUs The ZONE s...

Страница 10: ...occupied or temporary unoccupied override is selected the 369 operates the zone s in the selected override mode for 3 hours from the time the selection is made Once completed the control reverts to t...

Страница 11: ...ther items In cases where a restricted temperature range is required the RTU s range can be limited by changing the access level of the RTU Remote indoor sensors can be connected to the 063 to average...

Страница 12: ...ittings Before removing the knockouts check the wiring diagram and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections as the wires will interfe...

Страница 13: ...m pump circuit to the Sys Pmp terminal 17 and the second side of the pump circuit to the neutral N side of the 115 V ac power supply Zone Pumps and Zone Valves Note The zoning outputs are isolated ter...

Страница 14: ...to the Com and UnO Sw 4 and 1 terminals When these terminals short together the control registers an Unoccupied signal One Stage RTU and Indoor Sensor Connections RTUs and indoor sensors provide indoo...

Страница 15: ...or sensor is used connect the two wires from the sensor to the Com and Indr 4 terminals 24 and 27 Note If an RTU is connected to tN1 4 an indoor sensor can not be connected to Indr 4 Zone 6 tN1 6 or I...

Страница 16: ...erminals 7 and 6 make sure power to the pump or valve circuit is off and install a jumper between the Com 1 2 and Zn 1 terminals 7 and 6 When the zone circuit is powered up the zone pump should turn o...

Страница 17: ...he unlocked position to the locked position As long as the DIP switch is in the locked position the access level of the control or tekmar Net tN1 tN2 device can no longer be viewed or adjusted in its...

Страница 18: ...oom air temperature of zone 6 This is the signal that is being received from a zone control OFF 30 to 110 F OFF 1 to 43 C This is the signal that is being sent to a reset or additional zone control OF...

Страница 19: ...the zone number in the bottom of the display 369 Zone Adjust Menu 1 of 2 0 10 to 3 00 hr Default 0 30 hr NONE STRT Default NONE 0 30 to 4 00 min Default 3 00 min 0 10 to 2 00 min Default 0 30 min OFF...

Страница 20: ...was last cleared The total number of Cooling relay running hours since this item was last cleared The total number of Zn 1 relay running hours since this item was last cleared The total number of Zn 2...

Страница 21: ...r will increase if there is a lowering of the input voltage beyond the control s usable range This item can also be used as an indication of the quality of the power source L T D I N S T A D V Range A...

Страница 22: ...switch Setback C C C C Occ 2 UnOcc 2 to 11 50 PM or to 23 50 Default to 11 50 PM or to 23 50 Default to 11 50 PM or to 23 50 Default Time when the first occupied period begins every day 7DAY 24h 24hr...

Страница 23: ...002 When using display RTUs several items related to the system are no longer available in the control s User Interface These items are available only in the RTU s User Interface Also the number of i...

Страница 24: ...tment in the LTD access level MODE OFF and DIP switch Setback The desired cooled room air temperature during an occupied period Note There is only a 3 F 1 C adjustment in the LTD access level RTU 6 an...

Страница 25: ...is an adjustable item If the air temperature measured by the RTU drops below this setting the control will display a warning message OFF 20 to 80 F OFF 7 to 27 C Default OFF Note To clear the recorded...

Страница 26: ...le refer to the Example given in the Schedule menu of the 369 Note To skip an event during a schedule select the Null event Use the arrow keys to select the Time between 11 50 PM and 12 00 AM is displ...

Страница 27: ...utes while the test sequence is paused the control exits the entire test routine If the test sequence is paused the Test button can be pressed again to advance to the next step This can also be used t...

Страница 28: ...tch the piping of the system This is a relatively simple step that tends to be overlooked however it can often save hours of time troubleshooting a system Note flow directions in the system paying clo...

Страница 29: ...te Access level must be ADV in order to clear the error The control was unable to read a piece of information stored in the Miscellaneous Menu Because of this the control was required to load the fact...

Страница 30: ...nu Because of this the control was required to load the factory settings into all of the items in the Adjust menu The control will stop operation until all of the items available in the Adjust menu of...

Страница 31: ...o clear the error message The Remote 1 Sensor attached to RTU 1 is being read as a short circuit RTU 1 will continue operation using all remaining sensors If all of the sensors are unavailable the con...

Страница 32: ...The purchaser by taking receipt of the tekmar product product acknowledges receipt of the terms of the warranty and acknowledges that it has read and understands same tekmar warrants each tekmar prod...

Отзывы: