High Mass Radiant (1) 

This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum
pour. This heating system has a large thermal mass and is slow acting.
Default values: MIX DSGN = 120

°

F (49

°

C), MIX MAX = 140

°

F (60

°

C), MIX MIN = OFF

Low Mass Radiant (2) 

This type of radiant heating system is either attached to the bottom of a wood sub-floor,
suspended in the joist space, or sandwiched between the sub-floor and the surface.
This type of radiant system has a relatively low thermal mass and responds faster than
a high mass system.
Default values: MIX DSGN = 140

°

F (60

°

C), MIX MAX = 160

°

F (71

°

C), MIX MIN = OFF

Fancoil (3) 

A fancoil terminal unit or air handling unit (AHU) consists of a hydronic heating coil and
either a fan or blower. Air is forced across the coil at a constant velocity by the fan or
blower, and is then delivered into the building space.
Default values: MIX DSGN = 190

°

F (88

°

C), MIX MAX = 210

°

F (99

°

C),

MIX MIN = 100

°

F (38

°

C)

Fin–tube Convector (4) 

A convector terminal unit is made up of a heating element with fins on it. This type of
terminal unit relies on the natural convection of air across the heating element to deliver
heated air into the space. The amount of natural convection to the space is dependant
on the supply water temperature to the heating element and the room air temperature.
Default values: MIX DSGN = 180

°

F (82

°

C), MIX MAX = 200

°

F (93

°

C), MIX MIN = OFF

Radiator (5) 

A radiator terminal unit has a large heated surface that is exposed to the room. A radia-
tor provides heat to the room through radiant heat transfer and natural convection.
Default values: MIX DSGN = 160

°

F (71

°

C), MIX MAX = 180

°

F (82

°

C), MIX MIN = OFF

Baseboard (6) 

A baseboard terminal unit is similar to a radiator, but has a low profile and is installed at
the base of the wall. The proportion of heat transferred by radiation from a baseboard is
greater than that from a fin-tube convector.
Default values: MIX DSGN = 150

°

F (66

°

C), MIX MAX = 170

°

F (77

°

C), MIX MIN = OFF

Section B3: Advanced

MIXING INDOOR (MIX INDR) 

The MIX INDR is the room temperature used in the original heat loss calculations for the building. This setting establishes the
beginning of the 

Characterized Heating Curve for the mixing zones.

MIXING DESIGN (MIX DSGN) 

The MIX DSGN temperature is the supply water temperature required to heat the mixing zones when the outdoor air is as cold as the
OUTDR DSGN temperature.

MIXING MAXIMUM (MIX MAX) 

The MIX MAX sets the highest water temperature that the control is allowed to calculate as the MIX TARGET temperature. If the
control does target the MIX MAX setting, and the MIX temperature is near the MIX MAX, the MAX segment will be displayed in the
LCD while either the MIX TARGET temperature or the MIX temperature is being viewed.

Содержание Mixing Control 361

Страница 1: ...Demand Signal Input tekmar Timer Optional Input Indoor Sensor Optional Output Variable Speed Driven Pump Input Universal Sensor Included Press the Item buttons simultaneously for 1 sec to enter the A...

Страница 2: ...ommend reading Section A General Operation of the Sequence of Operation as this contains important information on the overall operation of the control Then read the sub sections that apply to your ins...

Страница 3: ...s the current status of the control s inputs outputs and operation Item Field Displays an abbreviated name of the selected item Pump Displays when the mixing system pump is in operation Burner Display...

Страница 4: ...An outdoor sensor is not required during this mode of operation VARIABLE SPEED A standard wet rotor circulator is connected to the 361 on the Var Pmp and N terminals 7 and 8 The 361 increases or decr...

Страница 5: ...ction B1 General Section B2 Installer Section B3 Advanced Section B1 General MIXING DEMAND A mixing demand is required in order for the 361 to provide heat A mixing demand is generated by applying a v...

Страница 6: ...ET becomes the setpoint supply temperature that the control is to maintain The MIX TARGET temperature is set by the installer in the ADJUST menu An outdoor sensor is not required during this mode of o...

Страница 7: ...r temperature to the heating element and the room air temperature Default values MIX DSGN 180 F 82 C MIX MAX 200 F 93 C MIX MIN OFF Radiator 5 A radiator terminal unit has a large heated surface that...

Страница 8: ...ating system to satisfy this demand If the control is in setpoint mode the WWSD feature is not functional Section C Boiler Operation Section C1 General Operation Section C2 Boiler Sensor Placement Sec...

Страница 9: ...temperature directly but allows the boiler to operate at its operating aquastat setting when required If this mode of operation is selected the boiler pump should either operate continuously or be op...

Страница 10: ...and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections as the wires will interfere with safety dividers which should be installed at a later t...

Страница 11: ...oiler Contact The Boiler terminals 9 and 10 are an isolated output in the 361 There is no power available on these terminals from the control These terminals are to be used as a switch to either make...

Страница 12: ...rly test the wiring and sensors Test The Sensors In order to test the sensors the actual temperature at each sensor location must be measured A good quality digital thermometer with a surface temperat...

Страница 13: ...any installation or troubleshooting information supplied with the pump If the pump operates properly disconnect the power and remove the jumpers Boiler If the boiler circuit is connected to the Boiler...

Страница 14: ...uick Setup The quick setup can be used for both outdoor reset and setpoint operation To enter the installer programming mode set the Advanced Installer DIP switch to Installer OUTDOOR RESET Access the...

Страница 15: ...Use the or button to set the scale to F or C To exit the ADJUST menu press and release the Item button to advance to the ESC item Then either press the or button or leave the buttons alone for 20 seco...

Страница 16: ...culation for the heating system OUTDR DSGN OFF 70 F to 220 F 21 to 104 C B3 The design indoor air temperature used in the heat loss calculation for the heating system OUTDR DSGN OFF 35 to 100 F 2 to 3...

Страница 17: ...used to rapidly advance through the test sequence To reach the desired step repeatedly press and release the Test button until the appropriate device and segment in the display turn on Step 1 The inj...

Страница 18: ...ng close attentiontothelocationofpumps checkvalves pressurebypassvalves andmixingvalves Ensurecorrect flow direction on all pumps This is also a very useful step if additional assistance is required D...

Страница 19: ...IN adjustment is higher than 100 F 38 C the control operates the Boiler contact as a boiler enable see section C The boiler temperature is then limited by the operating aquastat If the BOIL MIN adjust...

Страница 20: ...tekmar representative for that territory If the address of the repre sentative is not known please request it from tekmar at the telephone number listed below All speci cations are subject to change w...

Отзывы: