background image

Copyright © D 361 - 

03/09

12 of 20

Indoor Sensor

If an indoor sensor is used, connect the two wires from the sensor
to the 

Com and Indr terminals (15 and 17). The indoor sensor is

used by the 361 to measure the room air temperature.

Unoccupied Switch

If an external timer (tekmar Timer 03

2

) or switch is used, connect the two wires from

the external switch to the 

UnO Sw and Com terminals (11 and 12). When these two

terminals are shorted together, the control registers an unoccupied signal.

STEP FIVE 

 TESTING THE WIRING 

Each terminal block 

must be unplugged 

from its header on the control before power is applied for testing. To remove a terminal block,

pull it straight down from the control.

The following tests are to be performed using standard testing practices and procedures, and should only be carried out by properly
trained and experienced persons.

A good quality electrical test meter, capable of reading from at least 0 - 300 V (ac) and at least 0 - 2,000,000 Ohms, is essential to
properly test the wiring and sensors.

Test The Sensors 

In order to test the sensors, the actual temperature at each sensor
location must be measured. A good quality digital thermometer with a
surface temperature probe is recommended for ease of use and ac-
curacy. Where a digital thermometer is not available, a spare sensor
can be strapped alongside the one to be tested and the readings
compared. Test the sensors according to the instructions in the Data
Brochure D 070.

Test The Power Supply 

Make sure exposed wires and bare terminals are not in contact with
other wires or grounded surfaces. Turn on the power and measure
the voltage between the 

Power L and Power N terminals (3 and 4)

using an AC voltmeter. The reading should be between 108 and
132 V (ac).

Test The Powered Inputs 

Mixing Demand

Measure the voltage between the 

Mixing Demand terminals (1 and

2). When the mixing demand device calls for heat, you should
measure between 20 and 260 V (ac) at the terminals. When the
mixing demand device is off, you should measure less than 5 V (ac).

V

V

1

2

Mixing

Demand

20 to 260 V (ac)

V

V

3

4

L

N

Power

108 to 132 V (ac)

15

16

17

Com

Indr

Out

13

14

Boil

Mix

12

Com

V

Timer Switch

11 12

UnO

Sw

Com

Содержание Mixing Control 361

Страница 1: ...Demand Signal Input tekmar Timer Optional Input Indoor Sensor Optional Output Variable Speed Driven Pump Input Universal Sensor Included Press the Item buttons simultaneously for 1 sec to enter the A...

Страница 2: ...ommend reading Section A General Operation of the Sequence of Operation as this contains important information on the overall operation of the control Then read the sub sections that apply to your ins...

Страница 3: ...s the current status of the control s inputs outputs and operation Item Field Displays an abbreviated name of the selected item Pump Displays when the mixing system pump is in operation Burner Display...

Страница 4: ...An outdoor sensor is not required during this mode of operation VARIABLE SPEED A standard wet rotor circulator is connected to the 361 on the Var Pmp and N terminals 7 and 8 The 361 increases or decr...

Страница 5: ...ction B1 General Section B2 Installer Section B3 Advanced Section B1 General MIXING DEMAND A mixing demand is required in order for the 361 to provide heat A mixing demand is generated by applying a v...

Страница 6: ...ET becomes the setpoint supply temperature that the control is to maintain The MIX TARGET temperature is set by the installer in the ADJUST menu An outdoor sensor is not required during this mode of o...

Страница 7: ...r temperature to the heating element and the room air temperature Default values MIX DSGN 180 F 82 C MIX MAX 200 F 93 C MIX MIN OFF Radiator 5 A radiator terminal unit has a large heated surface that...

Страница 8: ...ating system to satisfy this demand If the control is in setpoint mode the WWSD feature is not functional Section C Boiler Operation Section C1 General Operation Section C2 Boiler Sensor Placement Sec...

Страница 9: ...temperature directly but allows the boiler to operate at its operating aquastat setting when required If this mode of operation is selected the boiler pump should either operate continuously or be op...

Страница 10: ...and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections as the wires will interfere with safety dividers which should be installed at a later t...

Страница 11: ...oiler Contact The Boiler terminals 9 and 10 are an isolated output in the 361 There is no power available on these terminals from the control These terminals are to be used as a switch to either make...

Страница 12: ...rly test the wiring and sensors Test The Sensors In order to test the sensors the actual temperature at each sensor location must be measured A good quality digital thermometer with a surface temperat...

Страница 13: ...any installation or troubleshooting information supplied with the pump If the pump operates properly disconnect the power and remove the jumpers Boiler If the boiler circuit is connected to the Boiler...

Страница 14: ...uick Setup The quick setup can be used for both outdoor reset and setpoint operation To enter the installer programming mode set the Advanced Installer DIP switch to Installer OUTDOOR RESET Access the...

Страница 15: ...Use the or button to set the scale to F or C To exit the ADJUST menu press and release the Item button to advance to the ESC item Then either press the or button or leave the buttons alone for 20 seco...

Страница 16: ...culation for the heating system OUTDR DSGN OFF 70 F to 220 F 21 to 104 C B3 The design indoor air temperature used in the heat loss calculation for the heating system OUTDR DSGN OFF 35 to 100 F 2 to 3...

Страница 17: ...used to rapidly advance through the test sequence To reach the desired step repeatedly press and release the Test button until the appropriate device and segment in the display turn on Step 1 The inj...

Страница 18: ...ng close attentiontothelocationofpumps checkvalves pressurebypassvalves andmixingvalves Ensurecorrect flow direction on all pumps This is also a very useful step if additional assistance is required D...

Страница 19: ...IN adjustment is higher than 100 F 38 C the control operates the Boiler contact as a boiler enable see section C The boiler temperature is then limited by the operating aquastat If the BOIL MIN adjust...

Страница 20: ...tekmar representative for that territory If the address of the repre sentative is not known please request it from tekmar at the telephone number listed below All speci cations are subject to change w...

Отзывы: