DIP Switch Settings
The DIP Switch settings on the control are very important and should be
set to the appropriate settings prior to making any adjustments to the
control through the user interface. The DIP switch settings change the
items that are available to be viewed and / or adjusted in the user
interface.
ADVANCED / INSTALLER
The
Advanced / Installer DIP switch is used to select which items are available to be viewed and / or adjusted in the user interface.
30% ENABLE / 10% ENABLE
The position of the
30% Enable / 10 % Enable DIP switch determines at which pump output the control will close the Boiler contact under
normal conditions. This switch is only operational if the
Boiler Sensor DIP switch is set to Return. Refer to section C2.
BOILER SENSOR (RETURN / SUPPLY)
The
Boiler Sensor DIP switch selects the installation location for the boiler sensor. When the boiler sensor is installed on the supply side
of the boiler loop, the DIP switch must be set to
Supply. The boiler aquastat should be set at least 20°F (11°C) higher than the required
design boiler water temperature. The boiler is controlled as described in section C.
For systems where the 361 provides a heat demand to an external boiler control, the boiler sensor should be installed on the return side
of the boiler loop. When the boiler sensor is installed on the return side of the boiler loop, the DIP switch must be set to
Return. The 361
only enables the boiler when the output of the variable speed injection pump exceeds the boiler enable DIP switch setting. The
Boiler
contact is controlled as described in section C. The boiler’s operating temperature is controlled by its aquastat, or an external boiler reset
control.
Quick Setup
The quick setup can be used for both outdoor reset and setpoint operation. To enter the installer programming mode, set the
Advanced /
Installer DIP switch to Installer.
OUTDOOR RESET
Access the ADJUST menu by pressing and holding simultaneously for 1 second, all three buttons. The display will now show the word
ADJUST in the top right corner.
The ROOM OCC adjustment is the first item displayed. Use the or button to set the ROOM temperature.
The ROOM OCC setting is set to the desired room air temperature during the occupied (Day) mode.
Note
: To increase or decrease space temperature during the occupied (Day) mode, only adjust the ROOM
OCC setting.
Press and release the
Item
button to advance to the ROOM UNOCC adjustment. Use the or button to
set the desired temperature. The ROOM UNOCC setting is set to the desired room air temperature during
the unoccupied (Night) mode.
Note:
To increase or decrease space temperature during the unoccupied (Night) mode, only adjust the
ROOM UNOCC setting.
Press and release the
Item
button to advance to the OUTDR DSGN adjustment. Use the or button to
set the outdoor design temperature. The OUTDR DSGN setting is set to the typical coldest temperature of
the year.
Press and release the
Item
button to advance to the
Terminal Unit adjustment. Use the or button to select
the desired terminal unit. The terminal unit number corresponds to the type of terminal that is being used.
The table below lists the terminal units and their default values.
ADJUST
ROOM
°
F
OCC
UN
ADJUST
DSGN
OUTDR
°
F
ADJUST
Terminal Unit
ADJUST
ROOM
°
F
OCC
30% Enable
Return
10% Enable
Boiler Sensor
Supply
Installer
Advanced
150°F (66°C)
170°F (77°C)
OFF
MIX DSGN
MIX MAX
MIX MIN
Terminal Unit
190°F (88°C)
210°F (99°C)
100°F (38°C)
High Mass Radiant
(1)
120°F (49°C)
140°F (60°C)
OFF
Low Mass Radiant
(2)
Fancoil
(3)
140°F (60°C)
160°F (71°C)
OFF
Fin-tube Convector
(4)
180°F (82°C)
200°F (93°C)
OFF
Radiator
(5)
160°F (71°C)
180°F (82°C)
OFF
Baseboard
(6)