Press and release the
Item
button to advance to the units adjustment. Use the or button to set the scale
to
°
F or
°
C.
To exit the ADJUST menu, press and release the
Item
button to advance to the ESC item. Then either press
the or button, or leave the buttons alone for 20 seconds.
SETPOINT CONTROL
Access the ADJUST menu by pressing and holding simultaneously for 1 second, the
Item
, and buttons. The display will now show
the word ADJUST in the top right corner.
Press and release the
Item
button to advance to the OUTDR DSGN adjustment. Press and hold the button
until OFF is displayed.
Press and release the
Item
button to advance to the MIX TARGET adjustment. Use the or button to select
the desired temperature. The MIX TARGET setting is set to the desired setpoint supply temperature.
Press and release the
Item
button to advance to the units adjustment. Use the or button to set the scale
to
°
F or
°
C.
To exit the ADJUST menu, press and release the
Item
button to advance to the ESC item. Then either press
the or button, or leave the buttons alone for 20 seconds.
Section
Advanced
Installer
View
Menu (1 of 1)
Current outdoor air temperature as measured by the outdoor
sensor. This is also the default display for the control.
(OUTDR DSGN
≠
OFF)
-67 to 149
°
F
(-55 to 65
°
C)
Display
Description
Range
Current room air temperature as measured by the indoor sensor.
(Indoor sensor is present)
23 to 113
°
F
(-5 to 45
°
C)
B1
Current mixed supply water temperature as measured by the
mixing sensor.
14 to 266
°
F
(-10 to 130
°
C)
B3
Target mixed supply is the temperature the control is currently
trying to maintain at the mixing sensor.
---, 14 to 266
°
F
(---, -10 to 130
°
C)
B1
B2
B3
Current boiler temperature as measured by the boiler sensor.
(Boiler sensor is present)
14 to 266
°
F
(-10 to 130
°
C)