61
(54) Motor Mutual Inductance Lm
(Cn-60)
•
Set the motor Y-equivalent model mutual inductance in mH unit.
•
The default setting depends upon the type of inverter.
•
This value will be automatically set during autotuning. See “Motor parameter
autotuning selection” on page 100.
Note : The Induction Motor Y-equivalent model
I
d
I
q
L
m
Ls
R1
R2
s
s : slip
(55) Slip Compensation Gain
(Cn-61)
•
The parameter Cn-61 improves speed accuracy while operating with a load.
•
Usually, the setting Cn-61 need not be changed. Adjust the setting if the speed
accuracy is needed to improve.
•
When actual speed is low, increase the set value.
•
When actual speed is high, decrease the set value.