![TECO speecon 7200ma Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/teco/speecon-7200ma/speecon-7200ma_instruction-manual_1072473048.webp)
46
Function
Parameter
No.
Name
LCD display (English)
Setting range
Setting
Unit
Factory
Setting
Ref.
Page
Cn-45
PG Parameter
Cn-45= 0000.0
PG Parameter
0.0
∼
3000.0P/R 0.1P/R 0.0P/R
Cn-46
Pole no. of Motor
Cn-46= 04P
Motor Pole
2
∼
32P
2P
4 P
Cn-47
ASR Proportional
Gain 1
Cn-47= 0.00
ASR Gain 1
0.00
∼
2.55
0.01
0.00
Cn-48 ASR Integral Gain 1
Cn-48= 01.0s
ASR Intgl. Time 1
0.1
∼
10.0S
0.1s
1.0s
Cn-49
ASR Proportional
Gain 2
Cn-49= 0.02
ASR Gain 2
0.00
∼
2.55
0.01
0.02
Cn-50 ASR Integral Gain 2
Cn-50= 01.0s
ASR Intgl. Time 2
0.1
∼
10.0S
0.1s
1.0s
60
Cn-51
ASR Upper Bound
Cn-51= 05.0
%
ASR Up Bound
0.1
∼
10.0
%
0.1
%
5.0%
Cn-52
ASR Lower Bound
Cn-52= 00.1
%
ASR Low Bound
0.1
∼
10.0
%
0.1
%
0.1%
Cn-53
Excessive Speed
Deviation Detection
Level
Cn-53= 10
%
Sp.Deviat. Det.Level
1
∼
50
%
1
%
10%
Speed
feedback
control
Cn-54
Overspeed Detection
Level
Cn-54= 110
%
Over Sp.Det. Level
1
∼
120%
1
%
110%
60
Cn-55
PID Integral Upper
Bound
Cn-55= 100
%
PID I-Upper
0
∼
109
%
1
%
100%
PID
Control
Cn-56
PID Primary Delay
Time Constant
Cn-56= 0.0s
PID Filter
0.0
∼
2.5s
0.1s
0.0s
61
Cn-57
Motor Line-to-Line
Resistance (R1)
Cn-57= 02.233
Ω
Mtr LINE_R
0.001
∼
60.000
Ω
0.001
Ω
2.233
Ω
*4
Cn-58
Motor Rotor Equivalent
Resistance
(R2)
Cn-58= 01.968
Ω
Mtr ROTOR_R
0.001
∼
60.000
Ω
0.001
Ω
1.968
Ω
*4
Cn-59
Motor Leakage
Inductance (Ls)
Cn-59= 9.6mH
Mtr LEAKAGE_X
0.01
∼
200.00mH 0.01mH 9.6mH
*4
Cn-60
Motor Mutual
Inductance (Lm)
Cn-60= 149.7mH
Mtr MUTUAL_X
0.1
∼
6553.5mH 0.1mH
149.7mH
*4
Sensorless
Vector
Control
Cn-61
Slip Compensation
Gain
Cn-61= 1.00
SLIP GAIN
0.00
∼
2.55
0.01
1.00
61,
62
*1 These are for a 220V class inverter. Value(*1) for a 440V class inverter is double.
*2 These are for a 220V class inverter. Value(*2) for a 440V class inverter is double.
*3 The setting range is 10% ~200% of the inverter rated current.
*4 The factory setting values will vary based upon the inverter capacity selection (Sn-01)
value. In this case, the setting is for 4-pole, 220V, 60Hz, 1Hp TECO standard induction
motors.