112
C. Wiring for PG Feedback Use
The 7200MA inverter has a built-in PG interface, no external PG feedback option is
needed. An independent DC source of +12V should be provided from external source.
A(+)
A(-)
IP12
AC 200~240V
50/60 Hz
IP12
IG12
P
P
E
7200MA
P
Encoder
+12V
0V
1
2
3
4
Power Supply
(L)
(N)
FG
R/L1
S/L2
T/L3
E
V/T2
W/T3
IM
U/
T1
OPEN
PULL UP
PG
TP1
Fig. 50 Wiring of PG feedback
Note :
1.
P
: Isolated twisted cable wire.
2.
Notation for PG terminals
Terminal
Function
A(+)
A(-)
PG signal input terminal.
The voltage level is (H: 4~12V, L:
≤
1V).
Its Max. frequency is < 32767 Hz
IP12
IG12
Terminals feed in the (+12)VDC external power
source (+12V
±
10%, the Max. current is 40mA)
+12V
0V
(+12)V DC source (+12V
±
10%, min. 0.5A)
E
Inverter ground.
3.
Please refer to page 60, 60, 96 for more details on PG feedback.
4.
The A(+), A(-), IP12, IG12 terminals are integrated as CN2 in compact version.
(see page 9). The code No. of the wire is 4H339D0250001.
5.
The PG interface only allows the open-collector interface drive or comple-mentary
interface drive.
6.
The short pin of TP1 set to PULL UP position for open-collector interface (factory
setting) and set to OPEN position for complementary interface. The PG interface
only allows the open-collector interface drive or complementary interface drive.
7.
The shielded twisted-pair cable wire should be used between the inverter and
PG, its length should be less than 50 meters.