Chapter 3 Environment description and installation
3-7
3.3 Wiring Rules
3.3.1 Notice for wiring
A.
Tightening
torque:
Connect cables with a screwdriver or other suitable tools
per the tightening
torque
s
listed below.
Securing torque
Horsepower Power
source
Tightening
torque for TM1 terminal
0.25/0.5/1 100-120V
0.25/0.5/1 200-240V
0.74/0.1
(LBS-FT / KG-M)
8.66/10
(LBS-IN/KG-CM)
2/3 200-240V
1/2/3 380-480V
1.286/0.18
(LBS-FT/KG-M)
15.97/18
(LBS-IN/KG-CM)
B. Power wires:
Power wires connect to
terminals
L1(L), L2, L3 (N), T1, T2, T3, P and N.
Select power wire
in
accordance with the following criteria:
(1) Use wires with copper core only. Insulating materials with diameters
should be
based on
working conditions at
221
o
F (105
o
C)
.
(2) The minimum
nominal
voltage of 240Vac type
connectors
is 300V, and 480Vac type
connector
is 600V.
C. Control wire:
Control wire is connected to
the
TM2 control terminal.
Select
wire in accordance with the
following criteria:
(1) Use copper core only.
The
insulating materials with diameters
should be
based on working
conditions at
221
o
F (105
o
C)
.
(2) To avoid noise interference, do not route the control
wiring
in the same conduit with power
wires and motor
wiring
.
D. Nominal electrical specifications of the terminal block:
The following are nominal values of TM1:
Horsepower Power
source Volts
Amps
0.25 / 0.5 / 1
100-120V
0.25 / 0.5 / 1
200-240V
600
15
2 / 3
200-240V
1 / 2 / 3
380-480V
600 40
※
Note: Nominal values of input and output signals (TM2) – follow the specifications of class 2
wiring.