Chapter 4 Software index
4-24
F50 Low frequency voltage compensation, C14=000
Performance: During low frequency
Increase F50 setting value
to
increase output voltage and low frequency torque.
Decrease F50 setting value
to
decrease output voltage and low frequency torque.
• Output voltage/frequency curve pattern:
• Operating frequency range:
• During low frequency use:
When the motor output torque is
insufficient
, increase F50 setting value.
When the motor is
vibrating excessively
, decrease F50 setting value.
F51 Advanced parameter function
display
000:Disable access to advanced parameters ( Group C )
001:Enable access to advanced parameters ( Group C )
F51=000. Parameter group C can not be displayed or accessed.
F51=001. Enable display and access
to
parameter group C.
F52 Factory default
010: Reset parameters to factory default (50Hz)
020: Reset parameters to factory default (60Hz)
F53 Software version
F54 Fault records (Latest 3 times)
Advanced Parameters List (Group C parameters)
C00 Reverse run
000: Reverse enable
001: Reverse disable
When
F04=000 and C00=001, F03 (motor direction)
is disabled
, the inverter is set to forward
operation.
When
F04=001 or 002, and C00=001, reverse command is
disabled
.
F50
V
F
0~12HZ / 60HZ
0~10HZ / 50HZ
Figure 4-13 Low Frequency Voltage Compensation