Chapter 4 Software index
4-20
Multi-function analog output:
F26 Multi-function output analog type selection
001: Set frequency
002: Output frequency
003: DC voltage
004: Output current
005: PID feedback signal
F27 Multi-function analog output gain = 000 ~ 200%
0-10 Vdc output from
the
FM+ multi-function analog output terminal.
Output can be set to any of the above selections.
F27 is used to scale the output signal supplied to the externally connected analog device.
F26=005, PID Feedback. The analog input to terminal AIN (0-10vdc or 4-20mA), will be
outputted
from terminal FM+ as 0-10Vdc.
Note: Due to hardware limits, the max output voltage from FM+ terminal will be limited to 10V.
Keypad, jog, and preset frequency setting (MFIT):
Note1: Frequency selection will be made according to the setting of terminals S1-S4 & AIN and
also setting of parameters F11 – F15 as required.
Note2: Selected preset frequency values should be programmed in parameters F28- F36 as
required.
1) F11~F15=002-004 (Preset frequency Command 1~3)
When
the
run signal is applied and any of the selected multi-function input terminals is ON,
the inverter will run at the preset frequency according to the table below.
2) F11~F15=005 (Jog Frequency Command)
External input terminal is set to Jog operation.
When ON
, the inverter will run at Jog frequency.
Parameter
Description
Frequency range Factory default
F28
Preset frequency 1 (Hz)
00.0 - 200
05.0
F29
Preset frequency 2 (Hz)
00.0 - 200
05.0
F30
Preset frequency 3 (Hz)
00.0 - 200
10.0
F31
Preset frequency 4 (Hz)
00.0 - 200
20.0
F32
Preset frequency 5 (Hz)
00.0 - 200
30.0
F33
Preset frequency 6 (Hz)
00.0 - 200
40.0
F34
Preset frequency 7 (Hz)
00.0 - 200
50.0
F35
Preset frequency 8 (Hz)
00.0 - 200
60.0
F36
Jog frequency (Hz)
00.0 - 200
05.0