ii
Step3 Check motor rotation without load.
z
Press RUN Key. 7-segment Display will indicates 00.0to 05.0. Such value is the frequency
output value.
z
Check the operation direction of the motor.
IF the direction of the motor is incorrect:
Press STOP Key, turn off the AC power supply. After Power indicator LED is off,
change over theT1 and T2.
Supply the power again, then check the motor direction.
z
Press STOP key.
Step4 Check full speed at 50Hz/60Hz
z
Change the frequency with
¿
,
À
arrow mark , please press DATA/ENTER after setting
frequency.
z
Set frequency to 50Hz/60Hz according to the above regulations.
z
Press RUN Key, inspect the motor operation as motor accelerates to full load.
z
Press STOP Key, inspect the motor operation as motor deceleration.
Step5 Other settings
As for other function, please refer to 7300EV user manual.
Set acceleration time ………………………………… P. 4-9
Set deceleration time ………………………………… P. 4-9
Set upper frequency limit ….………………………... P. 4-12
Set lower frequency limit ……………………………. P. 4-12
Set motor rated current ………………………………P. 4-30
Set control mode (Vector, V/F) ………………………P. 4-26
Step6 vector Mode Settings
When the EV inverter is set to run in Vector Mode (C14=000), the motor parameters needs to
be set. The required in formation should be readily available on the nameplate of the motor.
(Motor kw=0.75
¯
HP)
The parameters to set for vector operation ave:
Motor Rated Current (Amps) (F43) See page 4-23
Motor Rated Voltage (Volts) (F44) See page 4-23
Motor Rated Frequency (Hz) (F45) See page 4-23
Motor Rated Power (KW) (F46) See page 4-23
Motor Rated Speed (RPM) (F47) See page 4-23
Additional Vector Mode Settings to adjust for optimum operations are:
Torque boost gain (F48) See page 4-23
Slip compensation gain (F49) See page 4-24
Low Frequency Voltage Compensation (F50) See page 4-25