LED display
Possible solutions
SE01
Range setting
error
Check parameter setting.
SE02
Digital input
terminal error
Check multi-function input
setting.
SE03
V/f curve error
Check V/F parameters
SE05
PID selection
error
Check the setting value of
parameters 10-00 and 10-
01.
Check the setting value of
10-33, 10-34 and 23-05.
HPErr
Model selection
error
Check inverter capacity
setting 13-00.
SE09
PI setting error
Check pulse input
selection (03-30) and PID
source (10-00 and 10-01).
FB
(flash)
PID feedback
breaking
Check feedback wiring
Replace feedback sensor.
USP
(flash)
Unattended
Start Protection
Remove run command or
reset inverter via multi-
function digital input (03-
00 to 03-07 = 17) or use
the RESET key on the
keypad to reset inverter.
Activate USP input and
re-apply the power.
LFPB
Low flow error
Check feedback signal is
correct and with right
connection.
Check if feedback value
is lower than limit of
minimum flow.
LED display
Possible solutions
HFPB
High flow error
Check feedback signal is
correct.
Check if feedback value
is lower than limit of
maximum flow.
L0PB
Low pressure
error
Check feedback signal is
correct and with
connection.
Check if feedback value
of pressure is lower than
limit of minimum
pressure.
HIPB
High pressure
error
Check feedback signal is
correct.
Check if feedback value
of pressure is lower than
limit of maximum
pressure.
LSCFT
Low suction
error
Check if water of supply
tank is enough, and water
supply is regular.
Check PID difference is
higher than its level or
current is lower than
output current level
FIRE
Fire override
mode
None
(Fire override mode is not
a kind of warning).
SE10
PUMP/HVAC
Setting error
Check pump selection of
inverter (23-02) and (23-
03) settings.
Check HVAC selection of
inverter (23-46) and (23-
47) settings.
COPUP
PUMP
Communication
Breaking Error
Check if it has setting
issue or is not properly
connected.
Parameter
Setting Error
Refer to the instruction
manual or this parameter
is selected to be disabled.
Warning of
Direct Start
Check the digital input
terminal and disconnect
it. Then reconnect the DI
terminal after the setting
delay time (07-05) ends.
External
Terminal Stop
Error
Remove the run command
from external terminal
Содержание F510 series
Страница 1: ......
Страница 55: ...1 1 1 1 R L1 S L2 R L1 S L2 T L3 U T1 V T2 W T3 40 IEC 61800 3 08 1 2 200V 100 400V 10 LC RC 1 3 13 00 25 11 01...
Страница 56: ...2 1 4 1 5 08 30 07 00 5 5 20Hp 15 1 6 25 10 40 60 95 RH...
Страница 57: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Страница 58: ...4 2 2 F510 F510 2 1 2 2 2 3...
Страница 93: ...39 4 4 PM 01 22 02 02 04 Reserved 05 06 Reserved 07 08 Reserved 09 22 02 10 Reserved 11 22 11 100...
Страница 100: ......