Chapter 2 Environment and Installation
2.1 System Diagram
~
~
~
Power Supply
Molded
Circuit
Breaker
Magnetic
Contactor
AC
Reactor
Fast
Acting
Fuse
Input Noise
Filter
Inverter
Ground
Induction
Motor
Ground
Output Noise
Filter
Power supply:
Make sure the correct voltage is applied to avoid damaging the
inverter.
Molded-case circuit breaker (MCCB) or fused disconnect:
A molded-case circuit breaker or fused disconnect must be installed
between the AC source and the inverter that conforms to the rated
voltage and current of the inverter to control the power and protect the
inverter.
Do not use the circuit breaker as the run/stop switch for the
inverter.
Ground fault detector / breaker:
Install a ground fault breaker to prevent problems caused by
current leakage and to protect personnel. Select current range up to
200mA, and action time up to 0.1 second to prevent high frequency
failure.
Magnetic contactor:
Normal operations do not need a magnetic contactor. When performing
functions such as external control and auto restart after power failure, or
when using a brake controller, install a magnetic contactor.
Do not use the magnetic contactor as the run/stop switch for
the inverter.
AC line reactor for power quality:
When inverters are supplied by a high capacity power source (>
600KVA), an AC reactor can be connected to improve the power
factor.
Install Fast Acting Fuse:
To protect peripheral equipment, install fast acting fuses in accordance
with the specifications in the instruction manual for peripheral devices.
Input Noise filter:
A filter must be installed when there are inductive loads affecting the
inverter. The inverter meets EMC standard when the special filter is
used. See the instruction manual for peripheral devices.
Inverter:
Output terminals T1, T2, and T3 are connected to U, V, and W terminals
of the motor. If the motor runs in reverse while the inverter is set to run
forward, swap any two terminals connections for T1, T2, and T3.
To avoid damaging the inverter, do not connect the output
terminals T1, T2, and T3 to AC input power.
Connect the ground terminal properly. (200V class: Rg <100
;
400V class: Rg <10
.)
Output Noise filter:
An output noise filter may reduce system interference and induced
noise.
Motor:
If the inverter drives multiple motors the output rated current of the
inverter must be greater than the total current of all the motors.
Содержание F510 series
Страница 1: ......
Страница 55: ...1 1 1 1 R L1 S L2 R L1 S L2 T L3 U T1 V T2 W T3 40 IEC 61800 3 08 1 2 200V 100 400V 10 LC RC 1 3 13 00 25 11 01...
Страница 56: ...2 1 4 1 5 08 30 07 00 5 5 20Hp 15 1 6 25 10 40 60 95 RH...
Страница 57: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Страница 58: ...4 2 2 F510 F510 2 1 2 2 2 3...
Страница 93: ...39 4 4 PM 01 22 02 02 04 Reserved 05 06 Reserved 07 08 Reserved 09 22 02 10 Reserved 11 22 11 100...
Страница 100: ......