Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
11-38
Deceleration
Start Voltage
of OV
Prevention
200V: 200~400V
400V: 400~800V
200V:
300
400V:
700
Note2
11-39
Deceleration
Stop Voltage
of OV
Prevention
200V: 300~400V
400V: 600~800V
220V:
350
440V:
750
Note2
11-40
OV
Prevention
Selection
0: Disable
1: OV
Prevention
Mode 1
2: OV
Prevention
Mode 2
3: OV
Prevention
Mode 3
0
Note2
11-41
Reference
Frequency
Loss
Detection
0: Deceleration
to Stop when
Reference
Frequency
Disappears
0
1: Operation is
Set by 11-42
when Reference
Frequency
Disappears
11-42
Reference
Frequency
Loss Level
0.0~100.0 80.0
11-43
Hold
Frequency
at Start
0.0~400.0
0.0
11-44
Frequency
Hold Time
at Start
0.0~10.0 0.0
11-45
Hold
Frequency
at Stop
0.0~400.0
0.0
11-46
Frequency
Hold Time
at Stop
0.0~10.0 0.0
11-47
EB
Deceleratio
n Time
0.0~25.5 0.0
*1
11-48
KEB
Detection
Level
200V: 190~210
200
400V: 380~420
400
11-49
11-50
Reserved
11-51
Braking
Selection of
Zero Speed
0: Disable
0
1: Enable
11-52
11-53
Reserved
11-54
Initialization
of
Cumulative
Energy
0: Do not Clear
Cumulative
Energy
0 *1
1: Clear
Cumulative
Energy
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
11-55
STOP Key
Selection
0: Stop Key is
Disabled when
the Operation
Command is not
Provided by
Keypad.
1
1: Stop Key is
Enabled when
the Operation
Command is not
Provided by
Keypad.
11-56
UP/DOWN
Selection
0: When
UP/DOWN in
Keypad is
Disabled, it will
be Enabled if
Press ENTER
after Frequency
Modification
0
1: When
UP/DOWN in
Keypad is
Enabled, it will
be Enabled after
Frequency
Modification
11-57
Reserved
11-58
Record
Reference
Frequency
0: Disable
0 *1
1: Enable
11-59
Gain of
Preventing
Oscillation
0.00~2.50 0.01
*7
11-60
Upper Limit
of Preventing
Oscillation
0~100 30
*7
11-61
Time
Parameter of
Preventing
Oscillation
0~100 0
*7
11-62
Prevention of
Oscillation
Selection
0: Mode 1
1: Mode 2
2: Mode 3
1 *7
11-63
Flux-
Strengtheni
ng Selection
0: Disable
1
Note1
1: Enable
11-64
Acceleration
Speed Gain
Adjustment
0.1~10.0 1.0
Note3
11-65
Target Main
Circuit
Voltage
200V: 200V~400V
370
Note3
400V: 400V~800V
740
11-66
2 Phase/ 3
Phase PWM
Switch
Frequency
6.00~60.00 20
Note3
11-67
Detection
Range at
Soft PWM
Function 2
0~12000 0
Note3
11-68
Detecting
Start
Frequency at
6.00~60.00 20
Note3
Содержание F510 series
Страница 1: ......
Страница 55: ...1 1 1 1 R L1 S L2 R L1 S L2 T L3 U T1 V T2 W T3 40 IEC 61800 3 08 1 2 200V 100 400V 10 LC RC 1 3 13 00 25 11 01...
Страница 56: ...2 1 4 1 5 08 30 07 00 5 5 20Hp 15 1 6 25 10 40 60 95 RH...
Страница 57: ...3 2 2 1 NFB AC NFB NFB NFB 200mA 0 1 V TYPE AC AC EMC R S T E...
Страница 58: ...4 2 2 F510 F510 2 1 2 2 2 3...
Страница 93: ...39 4 4 PM 01 22 02 02 04 Reserved 05 06 Reserved 07 08 Reserved 09 22 02 10 Reserved 11 22 11 100...
Страница 100: ......