3-66
•
During Running (Setting:00)
OFF
Run source OFF, inverter is off.
ON
Run source ON, or Run source OFF but residues output exists
•
Zero Speed (Setting : 01)
OFF Output frequency
≧
MIN. output frequency (Cn-07)
ON
Output frequency
<
MIN. output frequency (Cn-07)
•
Frequency Agree :
(Setting : 02)
•
Setting Frequency Agree :
(Setting : 03)
•
Output Frequency Detected 1 :
(Setting : 04)
•
Output Frequency Detected 2 :
(Setting : 05)
•
Refer frequency detection function on page 3-22.
•
Inverter Ready
(Setting : 06)
•
Undervoltage Detected
(Setting : 07)
•
When the DC link voltage of main circuit is lower than the UNDERVOLTAGE
DETECTION LEVEL (Cn-39), the output contact is in ‘ON’ state.
•
Output Blocked
(Setting : 08)
•
Run Command Mode
(Setting : 09)
OFF
Remote Mode
(Sn-04 = 1,2, or multi-function input terminal
g
~
j
is set as Local/remote control I
mode or Local/remote control II mode and contact terminal is OFF). Remote-SEQ
LED is light in LCD digital operator
ON
Local Mode
(Sn-04 = 0 multi-function input terminal
g
~
j
is set as Local/remote control I mode
and contact terminal is ON).Remote-SEQ LCD is OFF, run command is from LCD
digital operator
•
Frequency Command Mode (Setting : 10)
OFF
Remote mode
(Sn-05 = 1,2
,
or multi- function input terminal
g
~
j
is set as Local/remote control I
mode or Local/remote control II mode and contact terminal is OFF). Remote-REF
LED is light in LCD digital operator
ON
Local mode
(Sn-05 = 0 multi- function input terminal
g
~
j
is set as Local/remote control I mode
and contact terminal is ON). Remote-REF LED is OFF, run command is from LCD
digital operator