3-65
Selection
(Sn-30)
(15)
Multi-Function Output Terminal (DO1-DOG) Function Selection (Sn-31)
(16)
Multi-Function Output Terminal (DO2-DOG or R2A-R2C) Function Selection
(Sn-32)
Multi-function output terminal setting and its function as shown in Table 16.
Table 16
Multi-function output terminal function
Setting
Function
LCD Display
Description
00
During running
Running
ON : During running
01
Zero speed
Zero Speed
ON : Zero speed
02
Frequency agree
Frequency Arrive
Speed agree width: Cn-31
03
Setting frequency agree
Agreed F Arrive
ON : output frequency = ±Cn-29,
Speed agree width: Cn-31
04
Output frequency detection1
Freq. Det. 1
ON : while ACC, -Cn-29 output freq. Cn-29
while DEC, -Cn-30 output freq. Cn-30
Speed agree width: Cn-31
05
Output frequency detection2
Freq. Det. 2
ON : while ACC, output freq Cn-29(or -Cn-29)
while DEC, output freq Cn-30(or -Cn-30)
Speed agree width: Cn-31
06
Inverter ready
Run Ready OK!
ON : READY
07
Undervoltage detected
Low Volt Detect
ON : Undervoltage detected
08
Output baseblocked
Output B.B.
ON : Output baseblocked
09
Run source mode
Run Source Operator ON : Run source from digital operator (Local mode)
10
Frequency command mode
Ref. Cmd. Operator
ON : Frequency command from digital operator
(Local mode)
11
Torque Detection 1, Contact A Tq. Detect 1 NO_Cont ON : Torque detection 1 detected, (Contact A)
12
Frequency command Invalid
Freq. Cmd. Invalid
ON : Frequency command Invalid
13
Fault
Fault
ON : Fault
14
Pulse signal output
Pulse Mul. Output
Only set by Sn-31, Sn-32 (terminal DO1-DOG)
15
Undervoltage alarm
Low Volt Alarm
ON : Undervoltage alarm
16
Inverter overheat
Inverter Over Heat
ON : Inverter Overheat
17
Motor overload
Motor Over Load
ON : Motor Overload
18
Inverter Overload
Inverter Over Load
ON : Inverter Overload
19
Fault retry
Fault Retry
ON : Retry
20
RS-485 communication fault
RS-485 Fault
ON : RS-485 communication fault
21
Timer function output
Timer Function
Signal delay output (.vs. timer function input)
22
RS-485 Communication
Application
Comm. Control
Extension Output Contact application
(Please refer to MA7200 RS-485 MODBUS /PROFIBUS
Application Manual’)
23
Torque Detection 1, Contact B Tq. Detect 1 NC_Cont ON : Torque detection 1 detected, (Contact B)
24
Torque Detection 2, Contact A Tq. Detect 2 NO_Cont ON : Torque detection 2 detected, (Contact A)
25
Torque Detection 2, Contact B Tq. Detect 2 NC_Cont ON : Torque detection 2 detected, (Contact B)