3-41
Table 11
460V
Class Inverter Capacity Selection
Sn-01 setting
021
022
023
024
025
026
027
CT(Sn-61
=
0)
VT(Sn-61
=
1)
Item name
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
Inverter rated capacity (KVA)
2.2
3.4
4.1
7.5
10.3
12.3
20.6
Inverter rated current
(A)
2.6
4
4.8
8.7
12
15
24
Max. applicable capacity (HP)
1
1
2
2
3
3
5.4
7.5
7.5
10
10
15
15
20
Cn-09
Motor rated current
(A)
1.7
1.7
2.9
2.9
4
4
7.3
10.2
10.2
12.6
12.6
18.6
18.6
24.8
Cn-12
Motor line
impedance (
Ω
)
22.927
22.927
9.628
9.628
6.333 6.333 2.735 1.776 1.776 1.151 1.151 0.634 0.634 0.436
Cn-13
Core loss torque
compensation (W)
64
64
108
108
142
142
208
252
252
285
285
370
370
471
Cn-34
Carrier freq. (kHz)
10
5
10
5
10
10
10
5
10
10
10
5
10
5
Cn-37
Min. baseblock time
(sec)
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.7
0.7
0.7
0.7
0.7
0.7
0.7
Fa
cto
ry Se
tti
ng
Sn-02
V/F curve
01
07
*1
01
07
*1
01
07
*1
01
07
*1
01
07
*1
01
07
*1
01
07
*1
Max. carrier freq. (kHz)
15
5
15
5
15
15
15
5
15
10
15
5
10
5
Sn-01 setting
028
029
030
031
032
033
034
CT(Sn-61
=
0)
VT(Sn-61
=
1)
Item name
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
CT
VT
Inverter rated capacity (KVA)
27.4
34
41
54
68
82
110
Inverter rated current
(A)
32
40
48
64
80
96
128
Max. applicable capacity (HP)
20
25
25
30
30
30
40
50
50
50
60
75
75
100
Cn-09
Motor rated current
(A)
24.8
31.1
31.1
36.3
36.3
36.3
48.7
59.0
59.0
59.0
70.5
80.0
80.0
114
Cn-12
Motor line
impedance (
Ω
)
0.436 0.308 0.308 0.239 0.239 0.239 0.164 0.133 0.133 0.133 0.110 0.074 0.074
0.027
Cn-13
Core loss torque
compensation (W)
471
425
425
582
582
582
536
641
641
641
737
790
790
1800
Cn-34
Carrier freq. (kHz)
10
5
10
5
10
10
10
5
10
10
10
5
10
5
Cn-37
Min. baseblock time
(sec)
0.7
0.7
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Fa
cto
ry Se
tti
ng
Sn-02
V/F curve
01
07
*1
01
07
*1
01
07
*1
01
07
*1
01
07
*1
01
07
*1
01
07
*1
Max. carrier freq. (kHz)
10
5
10
5
10
10
10
5
10
10
10
5
10
5
*1 Use the variable torque patterns when there is a quadratic or cubic relationship between the speed
and load, such as in fan or pump applications. The user can properly choose the desired (V/f)
patterns (Sn-02=04, 05, 06, or 07) based upon the load torque characteristics.
*2 In the fan or pump applications, the load torque have a quadratic or cubic relationship between the
speed and load. The inverter capacity rating can be increased to a value that doubles its own
specified capacity rating in some special case. But, due to the real hardware limitation,
230
V
1HP,
2HP, 3HP, 10HP, 25HP, 40HP
and
460
V
1HP, 2HP, 3HP, 30HP, 50HP
can not be adapted any larger
capacity.
(4)
V/F curve selection (Sn-02)
•
Set the inverter input voltage (Cn-01) first to match the power supply voltage. The
V/f curve can be set to ant of the following.
Sn-02 = 00~14: one of 15 pre-set curve patterns
= 15: V/F pattern can be set by the user through setting of Cn-01~Cn-08