3-81
(29)
The Cumulative Run Time Whenever The Output Power Is On (Un-31)
•
The parameter will record the cumulative operation time from power-on to power-
off. Its value is 0~65535 Hr. If the value exceeds 65535, it will restart from 0 again.
(30)
The EPROM Software Version (Un-32)
•
The parameter will specify the updated software version in this inverter.
(31)
Motor Speed While PG Feedback Is Set. (Un-33)
•
While PG feedback control is set, the motor speed can be monitored through Un-33.
(32)
PID Feedback Display (Un-34)
•
While PID Function is enabled, the PID feedback signal can be monitored through
Un-34. While PID Function is not enabled, the Un-34 will be zero.
•
The display content can be set by Cn-28, Sn-70, Bn-45 and Bn-46.
Cn-28 sets the decimal point position of Un-34.
Sn-70 sets the unit of Un-34.
Bn-45 is the equivalent value displayed for 0% PID Feedback.
Bn-46 is the equivalent value displayed for 100% PID Feedback.
•
Before monitoring PID feedback signal, be sure to set the value of Cn-28, Sn-70,
Bn-45 and Bn-46.