www.techsys.com.au
Version 1.3 11/12/11
27
C o r p o r a t io n
Out Delay Timer
When the pumps are called to turn off the delay for this
is governed by the OUT DELAYTIMER. It delays the
shutting down of additional pumps when the system
level is above the Cut In and pumps are attempting to shut down.
Restart Delay
.
When the system level rises above the Cut In Level the
first auto pump to start will be delayed by the RESTART
DELAY
No Flow Timer
If a flow switch is fiited and connected to a
programmable input which is programmed to “No Flow”
and pumps are running there should be flow detected by the Flow Switch. If there is No
flow the flow switch input is closed this timer delays a no flowshutdown by the given
amount.
Input Delay Timer
The SWO has the capacity to accept input
signals for various processes. This timer sets the delay
for reaction to those inputs. The specific inputs that are
controlled by this timer are:-
Outlined in the “Programmable Input Options”
Level Trip Low Delay
This setting delays the activation of the relevant Output
relay if programmed for Level Trip.
Level Trip High Delay
This setting delays the deactivation of the relevant
Output relay if programmed for Level Trip..
Note: The screens “Level Trip Low Delay” and “Level Trip High Delay” are only visible if at
least one output is set to “Trip point” in the OUTPUTS menu.
Out Delay Timer
XXX seconds
I/P Delay Timer
XXX seconds
Lvl Trip Lo Dly
XXX seconds
Lvl Trip Hi Dly
XXX seconds
Restart Delay
XXX seconds
No Flow Prot Dly
XXX seconds