Configuration of sensor using service adapter / Vertical menu description / Settings - Operation modes
DUT-E fuel level sensors. Operation manual. Version 8.1
©
Technoton, 2020
73
2) Message interval*
—
time period the sensor automatically send output message to the
tracking device.
Parameter value range is 1…
255 seconds with 1 second step. Default value is 1 second.
3) Automatic transmission mode*
–
defines sensor output message type:
•
Off
- no automatic message transmission, sensor waits for tracking device request;
•
HEX
- automatic message transmission in binary format (used by default);
•
ASCII
- automatic message transmission in text format;
•
ASCII EXT
- automatic message transmission in extended text format. Additional
Prefix
and
Postfix
configurable parameters are available for this mode to insert required
header or ending of the message.
4) Address
**
- provides
with network address when several operate via single bus
(network).
The following addresses are set by the
•
DUT-E 485 - two last digits of the sensor serial number;
•
DUT-E CAN/AF - 101.
5) Summator***
—
sets sensors network status when working in CAN summator mode
(see figure 49 e):
•
Off
- no need to summarize sensor values (default value);
•
Master
- should be selected for a sensor which has the highest decimal address in the
network;
•
Slave
- should be selected for all the other network sensors.
*
Only for DUT-E 232/485.
**
Only for DUT-E AF/CAN/485.
***
Only for DUT-E CAN.