TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 19

 

ramp, until the time “SSt” is reached or until the power overcomes 
the power calculated by the PID controller. 

SSt

 - SOFT START TIME (for PID control only): Duration time in 

hours and min. of the Soft-Start described on pa. “St.P”.  
To disable the Soft-Start function set par. “SSt” = OFF. 

 
GROUP  “ 

]

PAn” (PARAMETERS RELATIVE TO THE USER 

INTERFACE) : This contains the parameters relative to the key 
U and display functions.

 

Usrb -

 KEY U FUNCTION : Decides which function is associated to 

key U. The possible selections are : 
= noF : no function 
= tunE : Pushing the key for 1 sec. at least, it is possible to 
activate/deactivate the Auto-tuning or the Self-tuning 
= OPLO : Pushing the key for 1 sec. at least, it is possible to swap 
from the automatic control (rEG) to the manual one (OPLO) and vice 
versa. 
= Aac : Pushing the key for 1 sec. at least, it is possible to 
acknowledge the alarm.  
= ASi : Pushing the key for 1 sec. at least, it is possible to 
acknowledge an active alarm  
 = CHSP : Pushing the key for 1 sec. at least, it is possible to select 
one of the 4 pre-programmed Set Points on rotation.  
= OFF : Pushing the key for 1 sec. at least, it is possible to swap 
from the automatic control (rEG) to the OFF control (OFF) and vice 
versa. 

diSP - 

VARIABLE VISUALISED ON THE DISPLAY SV:

 

 Parameter 

trough which it’s possible to decide what is visualised on the display 
SV : the active Set Point (= SP.F), the Set Point active when there 
are ramps (= SP.o), the control power (= Pou),  the alarm thresholds 
AL1, 2 or 3 (= AL1, AL2 or AL3) or it can be switched off (OFF). 

Edit 

- FAST PROGRAMMING OF ACTIVE SET POINT AND 

ALARMS: This decides which are the Sets that can be programmed 
by the fast procedure. The parameter can be programmed as : 
=SE: The active Set Point can be modified while the alarm 
thresholds cannot be modified 
=AE :The active Set Point cannot be modified while the alarm 
thresholds can be modified 
=SAE: If the active Set Point or the alarm thresholds can be 
modified 
=SAnE: If the active Set Point or the alarm thresholds cannot be 
modified 
 

GROUP “ 

]

SEr”

 

(PARAMETERS RELATIVE TO THE SERIAL 

COMMUNICATION):

 

If the instrument is equipped with RS485 

serial communication these parameters allow device 
configuration for communication. 
Add

 – STATION ADDRESS IN CASE OF SERIAL 

COMMUNICATION : This is used to set the instrument address in 
the communication net. Programme a different number for each 
station, from 1 to 255. 

baud

 – TRANSMISSION SPEED (BAUD RATE): Set the data 

transmission speed of the network to which the instrument is 
connected. The possible selections are 1200, 2400, 9600, 19.2 
(19200), 38.4 (38400). 
All stations must  have the same transmission speed. 

PACS

 ACCESS TO PROGRAMMING THROUGH SERIAL PORT : 

Programming access. If programmed as "LoCL" this means that the 
instrument can only be programmed from the keyboard, if 
programmed as "LorE" it can be programmed from both the 
keyboards and serial line. 
 
 
 
 
 
 
 
 
 
 
 

 

6 - PROBLEMS, MAINTENANCE AND GUARANTEE

 

 
 6.1 - ERROR SIGNALLING 

In error conditions, the instrument provides an output power as 
programmed on par “OPE” and activates the desired alarms, if the 
relative parameters “ALni” have been programmed = yES.

 

 
6.2 - CLEANING 

We recommend  cleaning of the instrument with a slightly wet cloth 
using water and not abrasive cleaners or solvents which may 
damage the instrument. 

 
6.3 - GUARANTEE AND REPAIRS

 

The instrument is under warranty against manufacturing flaws or 
faulty material, that are found within 12 months from delivery date.  
The guarantee is limited to repairs or to the replacement of the 
instrument.  
The eventual opening of the housing, the violation of the instrument 
or the improper use and installation of the product will bring about 
the immediate withdrawal of the warranty’s effects.  
In the event of a faulty instrument, either within the period of 
warranty, or further to its expiry, please contact our sales 
department to obtain  authorisation for sending the instrument to our 
company.  
The faulty product must be shipped to TECNOLOGIC with a detailed 
description of the faults found, without any fees or charge for 
Tecnologic, except in the event of alternative agreements. 
 

7 - TECHNICAL DATA

 

 

7.1 – ELECTRICAL DATA

 

Power supply: 24 VAC/VDC, 100... 240 VAC +/- 10%  
Frequency AC: 50/60 Hz 
Power consumption: 10 VA approx. 
Input/s: 1 input for temperature probes: tc J,K,S ; RTD Pt 100 IEC; 
PTC KTY 81-121  (990

 Ω

 @ 25 °C); NTC 103AT-2 (10K

 @ 25 °C)  

or mV  signals 0...50 mV, 0...60 mV, 12 ...60 mV or normalized 
signals 0/4...20 mA, 0/1...5 V , 0/2...10 V.  
1 input for current transformer (50 mA max.) 

Error

 

Reason

 

Action 

 

- - - -

 

Probe interrupted 

uuuu

 

The measured variable 
is under the probe’s 
limits (under-range) 

oooo

 

The measured variable 
is over  the probe’s 
limits   (over-range) 

Verify the correct 
connection between 
probe and 
instrument and then 
verify the correct 
functioning of the 
probe 

ErAt

 

Auto-tuning not possible 
because the process 
value is higher (with 
“Func” =HEAt) than [SP- 
|SP/2|] or lower (with 
“Func” =CooL) than 
[SP+ |SP/2|] 

Swap the instrument 
to OFF control (OFF) 
and then to 
automatic control 
(rEG) in order to 
make the error 
message disappear. 
Once the error has 
been found, try to 
repeat  the auto-
tuning. 

noAt

 

Auto-tuning not finished 
within 12 hours 

Check the 
functioning of probe  
and actuator and try 
to repeat the auto-
tuning. 

LbA

 

Loop control interrupted 
(Loop break alarm) 

Check the working of 
probe  and actuator 
and swap the 
instrument to (rEG) 
control  

ErEP

 

Possible anomaly of the 
EEPROM memory 

Push key “P” 

Содержание TLK 43

Страница 1: ...also instructions for its maintenance and use we therefore recommend that the utmost attention is paid to the following instructions Though this manual has been issued with the greatest care TECNOLOG...

Страница 2: ...ualized on 4 green displays while the outputs status is indicated by 4 leds The instrument provides for the storage of 4 Set Points and can have up to 4 outputs relay type or can drive solid state rel...

Страница 3: ...e visualised on the SV display by pushing the P key Again by using the UP and DOWN keys it is possible to select the desired parameter and if the key P is pressed the display PV will show the paramete...

Страница 4: ...rogrammed on par SPLL and the one programmed on par SPHL Note in all the following examples the Set point is indicated as SP however the instrument will act according to the Set point selected as acti...

Страница 5: ...positive or negative offset that is simply added to the value read by the probe before visualisation which remains constant for all the measurements If instead it is desired that the offset set should...

Страница 6: ...ameters referring to the ON OFF control are contained in the group rEG This type of control can be obtained by programming par Cont On FS or On FA and works on the output programmed as 1 rEG depending...

Страница 7: ...at Power Ratio or relation between power of the element controlled by output 2rEG and power of the element controlled by output 1rEG 4 7 PID CONTROL FOR MOTORIZED ACTUATORS WITH TIME POSITIONING 1rEG...

Страница 8: ...grammed parameters To make the error ErAt disappear swap the instrument to the OFF control OFF and then turn it to automatic control rEG The Auto tuning cycle duration has been limited to 12 hours max...

Страница 9: ...ents etc where the set point has to be reached gradually in a predetermined time Once the instrument has reached the first Set Point SP1 it is possible to have automatic switching to the second Set Po...

Страница 10: ...band alarm OR MAXIMUM SET OF ALn ALARM THRESHOLD for low or high alarm HALn ALARM HYSTERESIS ALnd ALARM ACTIVATION DELAY in sec ALni ALARM BEHAVIOUR IN THE EVENT OF MEASUREMENT ERROR ALnt ALARM TYPE...

Страница 11: ...larm is active Enter group Hb and program which output the alarm signal has to address on parameter OHb The functioning mode of the alarm is instead defined on par HbF which can be set in the followin...

Страница 12: ...P1 2 By closing the contact connected to the digital input the set point SP2 is selected as being active while opening the contact selects the set point SP1 as active The function can only be activate...

Страница 13: ...l info please have a look at the KEY01 instruction manual 5 PROGRAMMABLE PARAMETERS Here following are described all the parameters available on the instrument Some of them could be not present or bec...

Страница 14: ...2 for high or low alarm AL2L 9999 9999 49 HAL2 Alarm AL2 hysteresis OFF 9999 1 50 AL2d Activation delay of alarm AL2 OFF 9999 sec OFF 51 AL2i Alarm AL2 activation in case of measuring error no yES no...

Страница 15: ...modes of the variable measured by the probe HCFG INPUT TYPE This permits selection of the input type thermocouples tc thermo resistances or thermistors rtd normalized signals in current I in voltage...

Страница 16: ...no_0 if one intends to use the beginning of the scale as being other than 0 4 mA or 2 V Ao1F ANALOGICAL OUTPUT OUT1 FUNCTION This determines the function of the OUT 1 output as control output 1 1 rEG...

Страница 17: ...LARM AL3 Similar to AL1d but referring to alarm AL3 AL3i ALARM AL3 ACTIVATION IN CASE OF MEASUREMENT ERROR Similar to AL1i but referring to alarm AL3 GROUP LbA PARAMETERS RELATIVE TO THE LOOP BREAK AL...

Страница 18: ...tched on the actuator must remain where it is no whether is must be taken to the maximum opening position oPEn or the maximum closing position cLoS Parameters relative to the ramps allowing the Set Po...

Страница 19: ...l stations must have the same transmission speed PACS ACCESS TO PROGRAMMING THROUGH SERIAL PORT Programming access If programmed as LoCL this means that the instrument can only be programmed from the...

Страница 20: ...ature 10 60 C 7 3 MECHANICAL DIMENSIONS PANEL CUT OUT AND MOUNTING mm 7 4 FUNCTIONAL FEATURES Control ON OFF single and double action PID PID for motorized actuators with time positioning Measurement...

Страница 21: ...99 9 999 9 19 99 99 99 1 999 9 999 0 10 V HCFG UoLt SEnS 0 10 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 2 10 V HCFG UoLt SEnS 2 10 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 7 6 INSTRUMENT ORDE...

Отзывы: