background image

 

TECNOLOGIC spa - TLK 43

 

- OPERATING INSTRUCTIONS - Vr.02 - ISTR 06267 - PAG. 10

 

It is advisable not to program a power “St.P” that is too high as the 
function is not deactivated when the automatic control power is 
found to be lower than the programmed one. 

2)

 If par. “St.P” = OFF and a value is set on par. “SSt” , at the switch 

on, the power calculated by the PID controller is divided by the time 
“SSt”, in order to calculate a ramp. The output power starts from 0 
and is progressively increased, depending on the calculated ramp, 
until the “SSt” time is reached or until the power overcomes the 
power calculated by the PID controller. 
To disable the Soft-Start function simply program par. “Sst” = OFF 
Whenever, a measurement errors occurs during the Soft-Start 
execution, the function is interrupted and the instrument gives an 
output power as programmed on par. “OPE”. 
If the measurement is restored, the Soft-Start is still deactivated. 
If it’s desired to activate the Autotuning with Soft-Start set par. 
“Auto”=4.  
The Autotuning will start automatically at the end of programmed 
Soft-Start cycle at the condition that the process value is lower (with 
“Func” =HEAt) than [SP- |SP/2|] or higher (with “Func” =CooL) than 
[SP+ |SP/2|]. 
 

4.14 – ALARM FUNCTION (AL1, AL2, AL3)

 

 

4.14.1 – ALARM OUTPUT CONFIGURATION

 

The alarms depend on the process value (AL1, AL2, AL3) and 
before setting them to work, it is necessary to know which output the 
alarm has to correspond to. 
First of all it is necessary to configure in the groups of parameters  

]

O ”,

 the parameters relative to the outputs required as alarm 

(“O1F” , “O2F” ,“O3F” ,“O4F”),

 

 programming the parameter relating 

to the desired output as follows : 

= ALno

 if the alarm output has to be ON when the alarm is active, 

while it is OFF when the alarm is not active 

= ALnc

 if the alarm output has to be ON when the alarm is not 

active, while it is OFF when the alarm is active  

Note:

 In the following examples the alarm’s number is generally 

indicated as 

 n

 

Access the group 

]

ALn”,

 relating to the alarm to be set and 

program which output the alarm signal must be sent to on par. 

“OALn”

The alarm functioning is instead defined by parameters : 

"ALnt "

 – ALARM TYPE 

"Abn"

 – ALARM CONFIGURATION 

“ALn”

 – ALARM THRESHOLD  

“ALnL”

 – LOW ALARM THRESHOLD (for band alarm) OR 

MINIMUM SET OF ALn ALARM THRESHOLD (for low or high 
alarm) 

“ALnH”

 - HIGH ALARM THRESHOLD (for band alarm) OR 

MAXIMUM SET OF ALn ALARM THRESHOLD (for low or high 
alarm) 

“HALn” - 

ALARM HYSTERESIS 

“ALnd”

 – ALARM ACTIVATION DELAY (in sec.) 

"ALni"

 – ALARM BEHAVIOUR IN THE EVENT OF 

MEASUREMENT ERROR 
 

"ALnt" – ALARM TYPE :

  the alarm output can behave in six 

different ways.

 

LoAb = ABSOLUTE LOW ALARM: The alarm is activated when the 
process value goes below the alarm threshold set on parameter 
"ALn”. With this mode is possible to program the minimum and the 
maximum set  of  “ALn” by “ALnL” and “ALnH” parameters.

 

 

HiAb = ABSOLUTE HIGH ALARM: The alarm is activated when the 
process value goes higher than the alarm threshold  set on 
parameter "ALn". With this mode is possible to program the 
minimum and the maximum set  of  “ALn” by “ALnL” and “ALnH” 
parameters. 

 

LHAb = ABSOLUTE BAND ALARM: The alarm is activated when 
the process value goes under the alarm threshold set on parameter 
"ALnL" or goes higher than the alarm threshold set on parameter 
"ALnH". 

 

LodE = DEVIATION LOW ALARM: The alarm is activated when the 
process value goes below the value [SP + ALn]. With this mode is 
possible to program the minimum and the maximum set  of  “ALn” 
by “ALnL” and “ALnH” parameters. 

 

HidE = DEVIATION HIGH ALARM: The alarm is activated when the 
process value goes above the value [SP + ALn]. With this mode is 
possible to program the minimum and the maximum set  of  “ALn” 
by “ALnL” and “ALnH” parameters. 

 

LHdE = DEVIATION BAND ALARM: The alarm is activated when 
the process value goes below the value [SP + ALnL] or goes above 
than the value [SP + ALnH] 

 

 
"

Abn" - ALARM CONFIGURATION:

 This parameter can assume a 

value between 0 and 15. 
The number to be set, which will correspond to the function desired, 
is obtained by adding the values reported in the following 
descriptions : 
ALARM BEHAVIOUR AT SWITCH ON: the alarm output may 
behave in two different ways, depending on the value added to par. 
“Abn”. 
+0 = NORMAL BEHAVIOUR: The alarm is always activated when 
there are alarm conditions. 
+1 = ALARM NOT ACTIVATED AT SWITCH ON: If, when switched 
on, the instrument is in alarm condition, the alarm is not activated. It 
will be activated only when the process value is in non-alarm 
conditions  and then back in alarm conditions. 

 

ALARM DELAY:  the alarm output may behave in two different ways 
depending on the value added to par. “Abn”. 
+0 = ALARM NOT DELAYED: The alarm is immediately activated 
when the alarm condition occurs. 
+2 = ALARM DELAYED: When the alarm condition occurs, delay 
counting begins, as programmed on par. “ALnd” (expressed in sec.) 
and the alarm will be activated only after the elapsing of that time. 

Содержание TLK 43

Страница 1: ...also instructions for its maintenance and use we therefore recommend that the utmost attention is paid to the following instructions Though this manual has been issued with the greatest care TECNOLOG...

Страница 2: ...ualized on 4 green displays while the outputs status is indicated by 4 leds The instrument provides for the storage of 4 Set Points and can have up to 4 outputs relay type or can drive solid state rel...

Страница 3: ...e visualised on the SV display by pushing the P key Again by using the UP and DOWN keys it is possible to select the desired parameter and if the key P is pressed the display PV will show the paramete...

Страница 4: ...rogrammed on par SPLL and the one programmed on par SPHL Note in all the following examples the Set point is indicated as SP however the instrument will act according to the Set point selected as acti...

Страница 5: ...positive or negative offset that is simply added to the value read by the probe before visualisation which remains constant for all the measurements If instead it is desired that the offset set should...

Страница 6: ...ameters referring to the ON OFF control are contained in the group rEG This type of control can be obtained by programming par Cont On FS or On FA and works on the output programmed as 1 rEG depending...

Страница 7: ...at Power Ratio or relation between power of the element controlled by output 2rEG and power of the element controlled by output 1rEG 4 7 PID CONTROL FOR MOTORIZED ACTUATORS WITH TIME POSITIONING 1rEG...

Страница 8: ...grammed parameters To make the error ErAt disappear swap the instrument to the OFF control OFF and then turn it to automatic control rEG The Auto tuning cycle duration has been limited to 12 hours max...

Страница 9: ...ents etc where the set point has to be reached gradually in a predetermined time Once the instrument has reached the first Set Point SP1 it is possible to have automatic switching to the second Set Po...

Страница 10: ...band alarm OR MAXIMUM SET OF ALn ALARM THRESHOLD for low or high alarm HALn ALARM HYSTERESIS ALnd ALARM ACTIVATION DELAY in sec ALni ALARM BEHAVIOUR IN THE EVENT OF MEASUREMENT ERROR ALnt ALARM TYPE...

Страница 11: ...larm is active Enter group Hb and program which output the alarm signal has to address on parameter OHb The functioning mode of the alarm is instead defined on par HbF which can be set in the followin...

Страница 12: ...P1 2 By closing the contact connected to the digital input the set point SP2 is selected as being active while opening the contact selects the set point SP1 as active The function can only be activate...

Страница 13: ...l info please have a look at the KEY01 instruction manual 5 PROGRAMMABLE PARAMETERS Here following are described all the parameters available on the instrument Some of them could be not present or bec...

Страница 14: ...2 for high or low alarm AL2L 9999 9999 49 HAL2 Alarm AL2 hysteresis OFF 9999 1 50 AL2d Activation delay of alarm AL2 OFF 9999 sec OFF 51 AL2i Alarm AL2 activation in case of measuring error no yES no...

Страница 15: ...modes of the variable measured by the probe HCFG INPUT TYPE This permits selection of the input type thermocouples tc thermo resistances or thermistors rtd normalized signals in current I in voltage...

Страница 16: ...no_0 if one intends to use the beginning of the scale as being other than 0 4 mA or 2 V Ao1F ANALOGICAL OUTPUT OUT1 FUNCTION This determines the function of the OUT 1 output as control output 1 1 rEG...

Страница 17: ...LARM AL3 Similar to AL1d but referring to alarm AL3 AL3i ALARM AL3 ACTIVATION IN CASE OF MEASUREMENT ERROR Similar to AL1i but referring to alarm AL3 GROUP LbA PARAMETERS RELATIVE TO THE LOOP BREAK AL...

Страница 18: ...tched on the actuator must remain where it is no whether is must be taken to the maximum opening position oPEn or the maximum closing position cLoS Parameters relative to the ramps allowing the Set Po...

Страница 19: ...l stations must have the same transmission speed PACS ACCESS TO PROGRAMMING THROUGH SERIAL PORT Programming access If programmed as LoCL this means that the instrument can only be programmed from the...

Страница 20: ...ature 10 60 C 7 3 MECHANICAL DIMENSIONS PANEL CUT OUT AND MOUNTING mm 7 4 FUNCTIONAL FEATURES Control ON OFF single and double action PID PID for motorized actuators with time positioning Measurement...

Страница 21: ...99 9 999 9 19 99 99 99 1 999 9 999 0 10 V HCFG UoLt SEnS 0 10 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 2 10 V HCFG UoLt SEnS 2 10 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 7 6 INSTRUMENT ORDE...

Отзывы: