Parameter

Description

Fuel

Feeder Flow

Feeder fuel delivering capability measured in pellets kg passed per minute.

Bunker Volume

Bunker volume in kg, used to calculate the bunker fuel level.

Service

Quantity of pellets burned after which a servicing is needed.

Energy

Energy density of the fuel in 

kWh/kg

.

Show KW

Allow the user to view the current power in absolute units (kW).

Ignition

Duration

Ignition attempt time. Includes the combined time for states Ignition and 
Kindle. After the attempt time expires, another retry is performed.

Retries

Number of ignition attempts. Exceeding it registers error 

Ignition failed

.

Flame Detect

Flame detection method:

Opto

: Light sensor, monitoring the flame intensity of the flame.

Flue

: Temperature of the flue gases.

Fan

Fumes fan power during the Ignition state.

Load Pellets

Feeder work time for the loading process in Ignition state.

Flue Delta

Relative temperature raise of flue gases compared to the start of ignition. 
Exceeding this temperature raise is considered for successful ignition.

Light Level

Light sensor level, exceeding it is considered for successful ignition.

Feeder2

Secondary feeder work time in percent, compared to main feeder.
For example if the parameter is set to 200%, then the secondary feeder will 
work twice longer than the main feeder.

Kindle

Fan

Fan power during Kindle state.

Feeder

Feeder time during Kindle state.

Flue Burning

Flue gases temperature, exceeding it marks successful Kindle state.

Light Time

Time, during which the level of the light sensor is constantly above 

Ignition

→ Light Level

. When time lapses, Kindle state is successful and over.

Lighter

Time to have the lighter output active in Kindle state.
The minimum value of the parameter is OFF.

Burn

Min Fan

Fan power on minimal work power.

Min Feeder

Feeder time on minimal work power.

Max Fan

Fan power on maximal work power.

Max Feeder

Feeder time on maximal work power.

Feeder2

Secondary feeder work time in percent, compared to main feeder.
For example if the parameter is set to 200%, then the secondary feeder will 
work twice longer than the main feeder.

Service parameters

13

Содержание tPell

Страница 1: ...tPell Pellet Combustion Controller Version 24 06 20...

Страница 2: ...tings 5 Week Timer 6 Info 6 Outputs 6 Date Time 7 Errors Actions 7 Principle of operation 8 Work mode 8 ON AUTO 8 OFF 8 States 8 Clean 8 Ignition 8 Kindle 8 Burn 8 Purge 8 Shutdown 9 Wait 9 Service pa...

Страница 3: ...mostat on or off if used Current temperature the measured temperature of the heated object Power the current operating power when burning in kW or relative units Fumes fan revolutions of the fan in Fe...

Страница 4: ...In AUTO mode the temperature is fixed by the week timer or the external thermostat Quick menu Fig 5 Quick menu To access the Quick menu press the button from the Main screen For navigation use the but...

Страница 5: ...press to save the change or to cancel the modification and revert to the previous value Heating Fig 8 Heating Boiler Temp boiler temperature set point The power is modulated in order to achieve the te...

Страница 6: ...decrease increase the temperature by 0 5 C as with by 2 C Info Fig 11 Information On this screen usage information is displayed Pellet counter for the pellets burned from the last reset In order to re...

Страница 7: ...creen title in brackets Errors 6 the number of the registered errors is shown Press over selected element to get detailed information about it To switch between views use the buttons Errors The error...

Страница 8: ...by monitoring the temperature of flue gases or the flame intensity depending on configuration On successful ignition it passes to the next state If the ignition time runs out before ignition is detec...

Страница 9: ...e state However the device will automatically transition to ON mode when the system needs to generate heat The device is in standby awaiting for some of the heated objects to need heating When all the...

Страница 10: ...pause Feeder run All parameters listed below that set the feeder time have the meaning of Feeder Fan Max Maximum revolutions per minute of the fumes fan It is used to calculate the percents that set...

Страница 11: ...Turn on temperature Pump Min Temp Pump Hyst Turn off temperature Pump Min Temp Pump Hyst Wait DHW ON Temperature difference below the set temperature in order to exit from Wait state Wait DHW OFF Temp...

Страница 12: ...e specified the shutdown is started Wait Temp ON Difference between the current and set temperature under which the device immediately transitions from Wait to Burn state Wait Temp OFF Difference betw...

Страница 13: ...ignition Exceeding this temperature raise is considered for successful ignition Light Level Light sensor level exceeding it is considered for successful ignition Feeder2 Secondary feeder work time in...

Страница 14: ...alue of the parameter is OFF Purge Period Purge period When the device is in Burn state and the set time expires it transitions to Purge state Upon completion it returns back to Burn state The minimum...

Страница 15: ...ted and saved After changing the service password you will be asked again for it in order to access the service menu Stop Work Fig 18 Stop Work The device can be forced to stop ignoring the conditions...

Страница 16: ...g stopped In Burn state a loss of flame is detected according to the flue gases temperature or light intensity Power failure The power was cut for time exceeding the recovery time Feeder blocked The c...

Страница 17: ...ture sensor room temperature thermostat NTC 10K t4 Temperature sensor DHW Light sensitive i1 Light sensor flame intensity Active level GND i2 Hall sensor for fan revolutions counting i3 Capacitive ind...

Страница 18: ...Fig 20 Connection 18 Connection...

Страница 19: ...h square opening sized 128 x 57 mm To mount the controller first unscrew the mounting bracket then put the controller in the opening Fix it in place by putting the bracket on the back side and fasten...

Страница 20: ...term is 24 months from date of sale The guarantee is not valid in following cases Incorrect installation Attempts to make repairs and or modifications of equipment by the customer Visible damages of...

Отзывы: