background image

Service parameters

Structure

Global

Boiler

DHW

Hardware Setup

Temperature Control

Fuel

Clean

Ignition

Kindle

Burn

Shutdown

Purge

Opto Calibration

Change Password

Stop Work

Outputs Test

Parameter menus

In the table below is a description of all service 

parameters. They are grouped into sub menus, noted
in table column 

Menu

.

The fumes fan power is set in percents of the 

maximal revolutions, as 100% = 

Fan Max

 and 0% = 

0 rpm.

Fuel feeding (operation of the feeder mechanism) 

is set in seconds with a precision of 0.1 sec and the 
stop time is determined of the total period as the 
sum of 

on time

 + 

stop time 

Feeder Period

.

Menu

Parameter

Description

Global

Feeder Period

Total time (run + pause). 

Feeder

 = run.

All parameters listed below, that set the feeder time, have the meaning of 

Feeder

.

Fan Max

Maximum revolutions per minute of the fumes fan. It is used to calculate the 
percents, that set the fan power.

Flue Max

Maximum flue gas temperature. Exceeding it, registers the error 

Overheat Flue

(if flue gases are used to detect flame).

Feeder Current

Maximum feeder current. Exceeding it, registers the error 

Feeder Blocked

.

Restore Power

If there is a power break for a period less than the parameter's value, then 
when the power is restored, the controller returns to Burn state. Otherwise it 
goes to Shutdown state and the error 

Power failure

 is registered if the 

parameter 

Power Failure

 is set.

Power Failure

Weather to register error, if the conditions, described for parameter 

Restore

Power

, are met. Registering an errors turns the work mode to OFF.

10

Service parameters

Содержание tPell

Страница 1: ...tPell Pellet Combustion Controller Version 24 06 20...

Страница 2: ...tings 5 Week Timer 6 Info 6 Outputs 6 Date Time 7 Errors Actions 7 Principle of operation 8 Work mode 8 ON AUTO 8 OFF 8 States 8 Clean 8 Ignition 8 Kindle 8 Burn 8 Purge 8 Shutdown 9 Wait 9 Service pa...

Страница 3: ...mostat on or off if used Current temperature the measured temperature of the heated object Power the current operating power when burning in kW or relative units Fumes fan revolutions of the fan in Fe...

Страница 4: ...In AUTO mode the temperature is fixed by the week timer or the external thermostat Quick menu Fig 5 Quick menu To access the Quick menu press the button from the Main screen For navigation use the but...

Страница 5: ...press to save the change or to cancel the modification and revert to the previous value Heating Fig 8 Heating Boiler Temp boiler temperature set point The power is modulated in order to achieve the te...

Страница 6: ...decrease increase the temperature by 0 5 C as with by 2 C Info Fig 11 Information On this screen usage information is displayed Pellet counter for the pellets burned from the last reset In order to re...

Страница 7: ...creen title in brackets Errors 6 the number of the registered errors is shown Press over selected element to get detailed information about it To switch between views use the buttons Errors The error...

Страница 8: ...by monitoring the temperature of flue gases or the flame intensity depending on configuration On successful ignition it passes to the next state If the ignition time runs out before ignition is detec...

Страница 9: ...e state However the device will automatically transition to ON mode when the system needs to generate heat The device is in standby awaiting for some of the heated objects to need heating When all the...

Страница 10: ...pause Feeder run All parameters listed below that set the feeder time have the meaning of Feeder Fan Max Maximum revolutions per minute of the fumes fan It is used to calculate the percents that set...

Страница 11: ...Turn on temperature Pump Min Temp Pump Hyst Turn off temperature Pump Min Temp Pump Hyst Wait DHW ON Temperature difference below the set temperature in order to exit from Wait state Wait DHW OFF Temp...

Страница 12: ...e specified the shutdown is started Wait Temp ON Difference between the current and set temperature under which the device immediately transitions from Wait to Burn state Wait Temp OFF Difference betw...

Страница 13: ...ignition Exceeding this temperature raise is considered for successful ignition Light Level Light sensor level exceeding it is considered for successful ignition Feeder2 Secondary feeder work time in...

Страница 14: ...alue of the parameter is OFF Purge Period Purge period When the device is in Burn state and the set time expires it transitions to Purge state Upon completion it returns back to Burn state The minimum...

Страница 15: ...ted and saved After changing the service password you will be asked again for it in order to access the service menu Stop Work Fig 18 Stop Work The device can be forced to stop ignoring the conditions...

Страница 16: ...g stopped In Burn state a loss of flame is detected according to the flue gases temperature or light intensity Power failure The power was cut for time exceeding the recovery time Feeder blocked The c...

Страница 17: ...ture sensor room temperature thermostat NTC 10K t4 Temperature sensor DHW Light sensitive i1 Light sensor flame intensity Active level GND i2 Hall sensor for fan revolutions counting i3 Capacitive ind...

Страница 18: ...Fig 20 Connection 18 Connection...

Страница 19: ...h square opening sized 128 x 57 mm To mount the controller first unscrew the mounting bracket then put the controller in the opening Fix it in place by putting the bracket on the back side and fasten...

Страница 20: ...term is 24 months from date of sale The guarantee is not valid in following cases Incorrect installation Attempts to make repairs and or modifications of equipment by the customer Visible damages of...