Service parameters
Structure
■
Global
■
Boiler
■
DHW
■
Hardware Setup
■
Temperature Control
■
Fuel
■
Clean
■
Ignition
■
Kindle
■
Burn
■
Shutdown
■
Purge
■
Opto Calibration
■
Change Password
■
Stop Work
■
Outputs Test
Parameter menus
In the table below is a description of all service
parameters. They are grouped into sub menus, noted
in table column
Menu
.
The fumes fan power is set in percents of the
maximal revolutions, as 100% =
Fan Max
and 0% =
0 rpm.
Fuel feeding (operation of the feeder mechanism)
is set in seconds with a precision of 0.1 sec and the
stop time is determined of the total period as the
sum of
on time
+
stop time
=
Feeder Period
.
Menu
Parameter
Description
Global
Feeder Period
Total time (run + pause).
Feeder
= run.
All parameters listed below, that set the feeder time, have the meaning of
Feeder
.
Fan Max
Maximum revolutions per minute of the fumes fan. It is used to calculate the
percents, that set the fan power.
Flue Max
Maximum flue gas temperature. Exceeding it, registers the error
Overheat Flue
(if flue gases are used to detect flame).
Feeder Current
Maximum feeder current. Exceeding it, registers the error
Feeder Blocked
.
Restore Power
If there is a power break for a period less than the parameter's value, then
when the power is restored, the controller returns to Burn state. Otherwise it
goes to Shutdown state and the error
Power failure
is registered if the
parameter
Power Failure
is set.
Power Failure
Weather to register error, if the conditions, described for parameter
Restore
Power
, are met. Registering an errors turns the work mode to OFF.
10
Service parameters