Parameter
Description
Е2 Input
E2
input function (registers error on active state of the input):
■
Chimney
: Chimney pressure sensor.
■
Door
: The door is opened. When the door is opened, the state is set to
idle and when is closed, the previous state is restored.
Е2 Invert
Invert the active state of the
E2
input (normally closed sensor).
Boiler t1
Heater temperature is sensed from physical input t1 instead of the default t2.
Refill
Running time of the refill output when a pellet bunker low level is registered.
Temperature Control
Thermostat
Thermostat is controlled by:
■
Room
: Room temperature.
■
Boiler
: Boiler temperature (water).
■
Ext NO
: External thermostat Normally-Opened.
■
Ext NC
: External thermostat Normally-Closed.
Wait Time ON
Time to transition to
Burn
from
Wait
state. If the device is in
Wait
state and
there is a need of heating more than the time specified, the ignition is started.
Wait Time OFF
Time to transition to
Wait
from
Burn
state. If the device is in
Burn
state and is
working in minimal power more than the time specified, the shutdown is
started.
Wait Temp ON
Difference between the current and set temperature, under which the device
immediately transitions from
Wait
to
Burn
state.
Wait Temp OFF
Difference between the current and set temperature, over which the device
immediately transitions from
Burn
to
Wait
state.
Wait Boiler
Exceeding the set boiler temperature by this, forces a transition to
Wait
state.
Power Levels
Number of power levels. Temperature control maximum power adjustment
step is 2. Increasing the number of power levels effects in more fluid
modulation, as decreasing it results in more rapid one.
Fuzzy Period
Period for calculating the power change (modulation step). The more inertia
the regulated object has, the bigger the period has to be and vice versa.
If the work power oscillates between minimum and maximum, when the set
point is reached, increase the period.
In case of a significant overshoot of the set point, decrease the period.
Flue Temp
Flue gases temperature set point. Temperature control algorithm alters the
power, so this set point is not exceeded. Keeping the flue gases temperature
guarantees that the overall efficiency of the unit will not drop below a certain
limit.
12
Service parameters