This manual provides guidance for the installation of AccuLoad preset models ST,
QT, N4 and SA. When installed following the guidelines contained in this manual, the
AccuLoad will provide many years of safe, accurate and reliable delivery control. This
manual addresses the requirements specific to the AccuLoad and it is assumed that
the installation designers and fabricators are familiar with the applicable industrial facil
-
ity construction standards specific to the particular facility. The ST and QT models are
designed for use in Class 1 Div 1, Zone 1 hazardous locations while the N4 and SA
models are designed for Class 1 Div 2 environments. If questions arise, please contact
our Field Service Response Center or Customer Support.
1.1
Warnings and Precautions
Before you begin please read all of the following warnings and cautions to reduce the
risk of injury, equipment damage or malfunction.
Emergency Shutdown
- The AccuLoad has an extensive set of built-in safety features.
IMPORTANT:
The AccuLoad should never be relied upon to act as the primary safety
system control for the flow valve and pump controls, i.e. emergency stop, overfill,
ground protection, etc. These should always be handled by separate systems specifi
-
cally designed for that application. For example Safety systems specifically to meet SIL
requirements. Any power control circuits from these external systems shall be wired in
series ahead of the AccuLoad to remove power to the ancillary devices.
Configuration
- The AccuLoad is shipped from the factory in a completely initialized
state and must be properly configured for the specific installation prior to operation. The
unit will not operate due to alarm conditions until the configuration is completed. Using
a PC running the AccuMate program is the best method to set the initial configuration,
but if AccuMate is not available, all configuration parameters are accessible through
the front panel.
Hazardous Voltages
- There are hazardous voltages involved in the installation
and maintenance of the AccuLoad and only qualified individuals should perform
this installation.
Hazardous Locations
- The ST and QT models are approved for use in an explosive
(Class I, Div. 1, Groups C & D and Zone 1 Ex d ia, IIB Gb) atmosphere but there are
specific installation methods required to produce a comprehensive explosion-proof
system. This manual provides guidance for the AccuLoad installation only. In general,
keeping the front cover bolted closed in accordance with the instructions in Appendix
(section 12) is the key to maintaining explosion protection.
Any modification of the AccuLoad housing invalidates the hazardous location
rating of the AccuLoad.
•
Do not replace the bolts in the front cover except with those supplied by the manufac
-
turer. Using unapproved bolts invalidates the explosion-proof rating of the enclosure
• Do not drill or machine the housing.
• Do not attempt to replace the touchscreen or glass except as part of the factory
supplied assembly.
Содержание ALIV-QT-XP
Страница 8: ...Page 8 MN06201 Issue Rev 0 1 2 20 Page intentionally left blank ...
Страница 12: ...Page 12 MN06201 Issue Rev 0 1 2 20 Page intentionally left blank ...
Страница 16: ...Page 16 MN06201 Issue Rev 0 1 2 20 Page intentionally left blank ...
Страница 62: ...Page 62 MN06201 Issue Rev 0 1 2 20 Page intentionally left blank ...
Страница 66: ...Page 66 MN06201 Issue Rev 0 1 2 20 Page intentionally left blank ...