2. Outdoor coil High Pressure Protection
The outdoor coil High Pressure protection prevents the rising of pressure in the outdoor coil
during cool mode operation
Protection
INPUTS (from indoor units)
OUTPUTS
Condition A
Condition B
RV1
(RV3)
RV2
(RV4)
CO1
(CO3)
CO2
(CO4)
OCT-A
(OCT-B)
ORV-A
(ORV-B)
CO-A
(CO-B)
OF-A
(OF-B)
SV-A1
(SV-B1)
SV-A2
(SV-B2)
SV-A3
(SV-B3)
High Pressure
Protection
Any
Any
Any
Any
> 55
RV1
(RV3)
X
Hi
X
X
X
Off
Off
On
On
= 50
X
ON
Hi / Lo
ON
ON
X
Termination of
Off
Off
On
Off
= 50
X
ON
Hi / Lo
ON
X
ON
HP Protection
Off
Off
Off
On
= 50
X
ON
Hi / Lo
X
ON
ON
Notes:
1. Protection Mode is activated when any of the condition A or condition B is satisfied.
•
In OCT high pressure protection, only the system that start the protection is under the
control of the protection routine. The other system will continue to work in normal
mode.
2. The OCT HP protection is triggered by the measured OCT-A (or OCT-B) only. The status of the
RV & CO inputs from the indoor units are not checked. This way, the protection can also handle
the abnormal situation caused by hardware failure, such as RV or COM output relay is defective
and
3. If the OF speed is marked as “Hi/Lo”, its speed is governed by the outdoor air thermistor as
explained before.
26
Содержание GR360M3R5TAA
Страница 15: ...Outdoor Unit GR360M3R5TAA 11...
Страница 24: ...8 2 Electric Wiring Diagrams Outdoor Unit GR360M3R5TAA Indoor Unit MCA90MR5TAA 20 Indoor Unit MCA180MR5TAA...
Страница 51: ...11 ARRANGEMENT OF ELECTRICAL COMPONENTS Terminal Plate Outdoor Unit GR360M3R5TAA 47 Electric Parts...
Страница 52: ...Outdoor Unit GR360M3R5TAA Parts Layout in Unit 48 Electronic Control Board Compressor A Compressor B...
Страница 53: ...Outdoor Unit GR360M3R5TAA 49 Solenoid valves lay out...