8
Controller PCB MSC1V1 (40V1-D)
Control circuit fuse 250 V– 3.15 A
Type Rotary (Hermetic)
Compressor model ... Number PH36VTRT ... 2
Nominal output W 1600 x 2
Compressor oil ... Amount cc DIAMOND MS32(N-1) ... 900 x 2
Coil resistance (Ambient temp. 25°C)
Ω
C – R : 1.08
C – S : 6.36
Type Internal
Overload relay ... Number UP3RE0302 ... 2
Safety
Operating Open °C 155 ± 5
devices temp. Close °C 90 ± 10
Operating amp.(Ambient temp. 25°C) Trip in 3 to 10 sec. at 54 A
Run capacitor µF 55 ... 2
... Number VAC 450 ... 2
Type Propeller
Number ... Dia. mm 2 ... ø460
Fan motor model ... Number KFC-6T-91C5P ... 2
No. of poles ... rpm (230 V,High) 6 ... 868
Nominal output W 100
Coil resistance (Ambient temp. 20°C)
Ω
WHT – BRN : 61 YEL - PNK: 17.7
WHT – YEL: 64.3
Safety Type Internal
protector
devices
Operating Open °C 130 ± 8
temp.
Close 79 ± 15
Run capacitor
µF 5.0
VAC 480
Coil
Aluminum plate fin / Copper tube
Rows
2
Fin pitch mm 2
Face area m
2
0.45 (each system)
External Finish
Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
outdoor Unit GR360M3R5TAA
Содержание GR360M3R5TAA
Страница 15: ...Outdoor Unit GR360M3R5TAA 11...
Страница 24: ...8 2 Electric Wiring Diagrams Outdoor Unit GR360M3R5TAA Indoor Unit MCA90MR5TAA 20 Indoor Unit MCA180MR5TAA...
Страница 51: ...11 ARRANGEMENT OF ELECTRICAL COMPONENTS Terminal Plate Outdoor Unit GR360M3R5TAA 47 Electric Parts...
Страница 52: ...Outdoor Unit GR360M3R5TAA Parts Layout in Unit 48 Electronic Control Board Compressor A Compressor B...
Страница 53: ...Outdoor Unit GR360M3R5TAA 49 Solenoid valves lay out...