2-2. Major Component Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. WSA –LTR
Controls Microprocessor
Control circuit fuse 250 V – 3.15 A
Remote Control Unit RC–2(WOA)
Type Cross–flow
Number ... Dia. and length mm 1 ... ø95 / L617
Fan motor model ... Number KFV4Q–11H5P -S... 1
No. of poles ... rpm (230 V, High) 4 ... 1190
Nominal output W 10
Coil resistance (Ambient temp. 20°C)
Ω
WHT – BRN : 561.8
WHT – VLT : 197.4
VLT – ORG : 63.4
ORG – YEL : 155.7
YEL – PNK : 115.9
Safety
Type Internal thermal fuse
devices Operating temp.
Open °C 145 ± 2
Close
—
Run capacitor
µF 0.8
VAC
440
Type
Stepping motor
Model
MP24GA1
Rating
DC 12 V
Coil resistance (Ambient temp. 25°C)
Ω
WHT – BLU (respectively 4 wires) : 380 ± 7%
Coil
Aluminum plate fin / Copper tube
Rows
2
Fin pitch
mm
1.4
Face area m
2
0.130
Heat
Exch. Coil
Flap Motor
Fan & Fan Motor
Controller
PCB
Indoor Unit MCA90MR5TAA
6
Содержание GR360M3R5TAA
Страница 15: ...Outdoor Unit GR360M3R5TAA 11...
Страница 24: ...8 2 Electric Wiring Diagrams Outdoor Unit GR360M3R5TAA Indoor Unit MCA90MR5TAA 20 Indoor Unit MCA180MR5TAA...
Страница 51: ...11 ARRANGEMENT OF ELECTRICAL COMPONENTS Terminal Plate Outdoor Unit GR360M3R5TAA 47 Electric Parts...
Страница 52: ...Outdoor Unit GR360M3R5TAA Parts Layout in Unit 48 Electronic Control Board Compressor A Compressor B...
Страница 53: ...Outdoor Unit GR360M3R5TAA 49 Solenoid valves lay out...