8. ELECTRICAL DATA
8-1. Electrical Characteristics
The values in the table below indicate the sum of indoor
units which are in running condition.
NOTE
230V Single phase 50 Hz
Indoor Unit MCA90 MCA180MR5TAA
Outdoor Unit GR360M3R5TAA
Rating Conditions:
Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions: Indoor Air Temperature 32°C DB / 23°C WB
Outdoor Air Temperature 46°C DB
Number of indoor unit
1 System 2 Systems
(A1+A2 ) (B) (A + B)
Rating Conditions
Running amp. A 9.8 9 18.8
Power input kW 2.1 2 4.1
Full Load Conditions
Running amp. A 11.2 11 22.2
Power input kW 2.5 2.5 5
230V Single phase 50 Hz
Cooling
Heating
Rating Conditions:
Indoor Air Temperature 20°C DB
Outdoor Air Temperature 7°C DB / 6°C WB
Full Load Conditions: Indoor Air Temperature 27°C DB
Outdoor Air Temperature 24°C DB / 18°C WB
Cooling
Heating
19
Number of indoor unit
1 System 2 Systems
(A1+A2 ) (B) (A + B)
Rating Conditions
Running amp. A 9.6 10.2 19.8
Power input kW 2.1 2.1 4.2
Full Load Conditions
Running amp. A 11 10.2 21.2
Power input kW 2.4 2.3 4.7