Models : GRV227M3C5, GRV340M3C5
IMPORTANT!
For your personal safety, be sure to read
and understand the following precautions
before servicing.
●
To avoid risk of injury when servicing the outdoor unit
(for instance, when replacing the compressor or
repairing a refrigerant leak), follow the procedure
below for the refrigerant circuits of unit A
and unit B.
— Procedure —
8
-1. Blue/green connector
attachment for servicing
8
-1-1.
Confirm mains power is switched OFF, then
disconnect the connectors (GRN/GRN) to
separate A and B. Then connect A connector
(GRN) with connector C (BLU). (Fig.9-1)
8
-1-2.
Provide a disconnect switch to the 3p terminal
plate. (Figs.9-2 and 9-3)
8
-1-3.
Turn the disconnect switch ON to supply power
(single-phase, 220-240 V) to the outdoor unit.
This makes it possible to force open two
solenoid valves (SVA and SVB) in the
refrigeration circuit. (Figs.9-2 and 9-3)
IMPORTANT!
The procedure given in "
8
-2" to "
8
-5" below
must be carried out with the two solenoid
valves SVA and SVB open.
33
8
. SPECIAL PRECAUTIONS WHEN SERVICING THE UNIT
Injuries can occur from burns or inhalation of
toxic gas if servicing is performed while
refrigerant remains in the refrigeration circuit.
This servicing includes disassembling brazed
tubing connections and removing any
refrigeration parts or components.
WARNING
Fig.1
Before
After
: CONNECTOR
4
5
8
GRN
BLU
• Condition at shipping
• Condition for operation
Terminal plate
B
A
C
4
5
8
GRN
BLU
• Condition at servicing
(Procedure "9-2" ~ "9-5")
Terminal plate
C
A
B
Fig.9-1
Содержание DKR5555C
Страница 20: ...GRV227M3C5 UNTIL31 12 2003 GRV340M3C5 FROM31 12 2003 5 2 ELECTRICWIRINGDIAGRAM SYSTEMWIRINGDIAGRAM 20...
Страница 21: ...GRV340M3C5 ELECTRICWIRINGDIAGRAM 21...
Страница 22: ...22 Outdoor Unit DKR5555C UNTIL 31 12 2002 Outdoor Unit DKR5555C FROM 01 01 2003...
Страница 23: ...23 Outdoor Unit DKR8585C UNTIL 31 12 2003 Outdoor Unit DKR8585C FROM 01 01 2003...