8
-5-4.
With a hex wrench, open the service valve little
by little to let liquid refrigerant enter the circuit.
(Figs.9-4 and 9-5)
●
Write down the gradation levels on the charging
cylinder before and after the charging. This allows
you to calculate the charging volume.
8
-5-5.
If it is not possible to completely charge the unit
with the proper amount of refrigerant, you can do
a additional charging after installing the units. At
that time, refrigerant should be recharged in the
liquid state a little at a time using the wide tube
service port, and the air conditioner should be
operating in COOLING mode during the entire
charging process.
●
Charging the unit with a large amount of
refrigerant at once may damage the compressor.
Always charge the unit at a constant charging rate
of about 100 g.
8
-6. Reattaching green connectors
for operation
8
-6-1.
Turn off the power source.
8
-6-2.
Connect the two green connectors to each other
as in the original state. (Fig.9-6)
NOTE
Charging
volume
Gradation
level before
charging
Gradation
level after
charging
=
–
NOTE
36
Remember to reattach the green connectors in
the original position. Otherwise, the system will
not operate correctly and damage may occur.
CAUTION
: CONNECTOR
4
5
8
GRN
BLU
• Condition at shipping
• Condition for operation
4
5
8
GRN
BLU
• Condition at servicing
(Procedure "9-2" ~ "9-5")
Terminal plate
Terminal plate
B
A
C
A
C
B
Before
After
Fig.9-6
1
2
3
4
5
6
7
8
Terminal plate
GRN
BLU
Power
Supply
Disconnect switch
(Field supply)
Charging cylinder
Open
Unit A
Unit B
Unit C
Hex wrench
GRV340M3C5
Fig.9-5
Содержание DKR5555C
Страница 20: ...GRV227M3C5 UNTIL31 12 2003 GRV340M3C5 FROM31 12 2003 5 2 ELECTRICWIRINGDIAGRAM SYSTEMWIRINGDIAGRAM 20...
Страница 21: ...GRV340M3C5 ELECTRICWIRINGDIAGRAM 21...
Страница 22: ...22 Outdoor Unit DKR5555C UNTIL 31 12 2002 Outdoor Unit DKR5555C FROM 01 01 2003...
Страница 23: ...23 Outdoor Unit DKR8585C UNTIL 31 12 2003 Outdoor Unit DKR8585C FROM 01 01 2003...