background image

TECDrive TEC-3 User Guide Revision 1.20 

 

www.tecmotors.co.uk/tecdrive 

9

 

 

3

 
M

e

ch

an

ical 
In

st

all

at

ion
 

3.

 

Mechanical Installation 

3.1.

 

General 

The TECDrive should be mounted in a vertical position only, on a flat, flame resistant, vibration free mounting using the integral mounting holes 
or DIN Rail clip (Frame Sizes 1 and 2 only). 
IP20 TECDrives must be installed in a pollution degree 1 or 2 environment only. 
Do not mount flammable material close to the TECDrive 
Ensure that the minimum cooling air gaps, as detailed in section 3.5 and 3.7 are left clear 
Ensure that the ambient temperature range does not exceed the permissible limits for the TECDrive given in section 9.1 
Provide suitable clean, moisture and contaminant free cooling air sufficient to fulfil the cooling requirements of the TECDrive 

3.2.

 

UL Compliant Installation 

Refer to section 9.4 on page 28 for Additional Information for UL Compliance. 

3.3.

 

Mechanical Dimensions and Mounting 

 IP20 Open Units 

 

 

Drive 

Size 

Weight 

Weight 

mm 

in 

mm 

in 

mm 

in 

mm 

in 

mm 

in 

mm 

in 

Kg 

Kg 

173 

6.81 

83 

3.27 

123 

4.84 

162 

6.38 

50 

1.97 

50 

1.97 

1.0 

1.0 

221 

8.70 

110 

4.33 

150 

5.91 

209 

8.23 

63 

2.48 

63 

2.48 

1.7 

1.7 

261 

10.28 

131 

5.16 

175 

6.89 

247 

9.72 

80 

3.15 

80 

3.15 

3.2 

3.2 

420 

16.54 

171 

6.73 

212 

8.35 

400 

15.75 

125 

4.92 

125 

4.92 

9.1 

9.1 

Mounting Bolts 

Frame Size 1 - 3 

4 x M5 (#8) 

Frame Size 4 

4 x M8 

Tightening Torques 

Frame Sizes 1 

 3 

Control Terminals 

0.5 Nm (4.5 lb-in) 

Power Terminals 

1 Nm (9 lb-in) 

Frame Size 4 

Control Terminals 

0.5 Nm (4.5 lb-in) 

Power Terminals 

2 Nm (18 lb-in) 

3.4.

 

Guidelines for Enclosure Mounting 

 IP20 Units 

IP20 drives are suitable for use in pollution degree 1 environments, according to IEC-664-1. For pollution degree 2 or higher environments, 
drives should be mounted in a suitable control cabinet with sufficient ingress protection to maintain a pollution degree 1 environment around 
the drive. 
Enclosures should be made from a thermally conductive material. 
Ensure the minimum air gap clearances around the drive as shown below are observed when mounting the drive. 
Where ventilated enclosures are used, there should be venting above the drive and below the drive to ensure good air circulation. Air should be 
drawn in below the drive and expelled above the drive. 
In any environments where the conditions require it, the enclosure must be designed to protect the TECDrive against ingress of airborne dust, 
corrosive gases or liquids, conductive contaminants (such as condensation, carbon dust, and metallic particles) and sprays or splashing water 
from all directions. 
High moisture, salt or chemical content environments should use a suitably sealed (non-vented) enclosure.  

The enclosure design and layout should ensure that the adequate ventilation paths and clearances are left to allow air to circulate through the 
drive heatsink. Invertek Drives recommend the following minimum sizes for drives mounted in non-ventilated metallic enclosures:- 

 

 

Drive 

Size 

Above & 

Below 

Either 

Side 

Between 

Recommended 
airflow 

 

mm 

in 

mm 

in 

mm 

in 

CFM (ft

3

/min) 

50 

1.97 

50 

1.97 

33 

1.30 

11 

75 

2.95 

50 

1.97 

46 

1.81 

22 

100 

3.94 

50 

1.97 

52 

2.05 

60 

100 

3.94 

50 

1.97 

52 

2.05 

120 

Note : 

Dimension Z assumes that the drives are mounted side-by-side with 
no clearance. 
 
Typical drive heat losses are 3% of operating load conditions. 
 
Above are guidelines only and the operating ambient temperature of 
the drive MUST be maintained at all times. 

Содержание TECDrive TEC -3-120070-101 Series

Страница 1: ...uide Revision 1 20 www tecmotors co uk tecdrive 1 1 Quick Start Up TECDrive User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 22kW 0 5 30HP 110 480V Distributed by TEC Electric Motors www tecm...

Страница 2: ...TECDrive TEC 3 User Guide Revision 1 20 2 www tecmotors co uk tecdrive 1 Quick Start Up Di and Operating Instructions...

Страница 3: ...ions 14 4 9 Motor Thermal overload Protection 15 4 10 EMC Compliant Installation 15 4 11 Optional Brake Resistor 15 5 Operation 16 5 1 Managing the Keypad 16 5 2 Operating Displays 16 5 3 Changing Par...

Страница 4: ...g from transport receipt of delivery installation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installatio...

Страница 5: ...normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the...

Страница 6: ...before connecting the supply 9 5 EMC Filter Disconnect 28 7 Check the supply cable and motor cable for faults or short circuits 8 Route the cables 9 Check that the intended motor is suitable for use...

Страница 7: ...to Stop Connect a potentiometer 5k 10k between terminals 5 6 and 7 as shown o Adjust the potentiometer to vary the speed from P 02 0Hz default to P 01 50 60 Hz default Quick Start IP66 Switched Switc...

Страница 8: ...1 0 75 1 4 3 1 TEC 3 120070 1F1 TEC 3 120070 101 1 5 2 7 1 TEC 3 220070 1F4 TEC 3 220070 104 1 5 2 7 2 TEC 3 220105 1F4 TEC 3 220105 104 2 2 3 10 5 2 N A TEC 3 320153 104 4 0 5 15 3 3 200 240V 10 3Pha...

Страница 9: ...e suitable for use in pollution degree 1 environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingres...

Страница 10: ...section 9 1 The drive must be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should b...

Страница 11: ...nduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On the...

Страница 12: ...d must be connected to system ground Ground impedance must conform to the requirements of national and local industrial safety regulations and or electrical codes The integrity of all ground connectio...

Страница 13: ...mended to be installed in the supply line for drives where any of the following conditions occur o The incoming supply impedance is low or the fault level short circuit current is high o The supply is...

Страница 14: ...STOP Run in Hand 0 4 Run in Hand Speed controlled from the Local POT Run in Auto 0 Speed controlled using Analog input 2 e g from PLC with 4 20mA signal Run in Speed Control STOP Run in PI Control 5 1...

Страница 15: ...ry Supply Cable Type Motor Cable Type Control Cables Maximum Permissible Motor Cable Length C16 Shielded1 Shielded1 5 Shielded4 1M 5M7 C2 Shielded2 Shielded1 5 5M 25M7 C3 Unshielded3 Shielded2 25M 100...

Страница 16: ...nds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings press and hold Up Down and Stop buttons for 2 seconds The display will show Drive is enabled r...

Страница 17: ...from the motor nameplate enables the slip compensation function and the TECDrive display will now show motor speed in RPM All speed related parameters such as Minimum and Maximum Speed Preset Speeds e...

Страница 18: ...ncy 4 32 8 kHz Sets maximum effective switching frequency of the drive If rEd is displayed when the parameter is viewed the switching frequency has been reduced to the level in P00 32 due to excessive...

Страница 19: ...Power On or Reset the drive will automatically start if Digital Input 1 is closed To Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The numbers of restart att...

Страница 20: ...mmunication An suffix means that the drive will coast stop output immediately disabled but will not trip P 37 Access Code Definition 0 9999 101 Defines the access code which must be entered in P 14 to...

Страница 21: ...3 Advanced Parameters Par Description Minimum Maximum Default Units P 51 Motor Control Mode 0 5 0 0 Vector speed control mode 1 V f mode 2 PM motor vector speed control 3 BLDC motor vector speed contr...

Страница 22: ...cess data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of 85 C...

Страница 23: ...T STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which must be Normally Closed When the input opens the drive trips show...

Страница 24: ...ntrol Mode P 12 3 4 7 8 or 9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 14 1 STOP ENABLE PI Speed Re...

Страница 25: ...emperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance P Loss Input Phase Loss Trip SC trp Communications Loss Trip...

Страница 26: ...gh Run Enable Bit 1 Low Decel Ramp 1 P 04 High Decel Ramp 2 P 24 Bit 2 Low No Function High Fault Reset Bit 3 Low No Function High Coast Stop Request 2 R W Modbus Speed reference setpoint 0 5000 Setpo...

Страница 27: ...8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 9 5 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2 2 2 3 12 1 16 17 5 8 8 10 5 50 3 4 5 20...

Страница 28: ...cording to section 4 3 Suitable Power and motor cables should be selected according to the data shown in section 9 2 and the National Electrical Code or other applicable local codes Motor Cable 75 C C...

Страница 29: ...sed over 10 C in order to start the drive 10 Factory Default parameters loaded 11 External trip E trip requested on digital input 3 Normally closed contact has opened for some reason If motor thermist...

Отзывы: