TECDrive TEC-3 User Guide Revision 1.20 

 

www.tecmotors.co.uk/tecdrive 

19

 

 

6

 
Pa
ra

m

e

ter

Par. 

Description 

Minimum 

Maximum 

Default 

Units 

P-25 

Analog Output Function Select 

11 

Digital Output Mode. Logic 1 = +24V DC  

0: Drive Enabled (Running)

. Logic 1 when the TECDrive is enabled (Running) 

1: Drive Healthy

. Logic 1 When no Fault condition exists on the drive 

2: At Target Frequency (Speed)

. Logic 1 when the output frequency matches the setpoint frequency 

3: Drive Tripped

. Logic 1 when the drive is in a fault condition 

4

:

 Output Frequency >= Limit

. Logic 1 when the output frequency exceeds the adjustable limit set in P-19 

5

:

 Output Current >= Limit

. Logic 1 when the motor current exceeds the adjustable limit set in P-19 

6

:

 Output Frequency < Limit

. Logic 1 when the output frequency is below the adjustable limit set in P-19 

7

:

 Output Current < Limit

. Logic 1 when the motor current is below the adjustable limit set in P-19 

Analog Output Mode 

8: Output Frequency (Motor Speed)

. 0 to P-01, resolution 0.1Hz 

9: Output (Motor) Current

. 0 to 200% of P-08, resolution 0.1A 

10: Output Power

. 0 

 200% of drive rated power 

11: Load Current

. 0 

 200% of P-08, resolution 0.1A 

P-26 

Skip frequency hysteresis band 

0.0 

P-01 

0.0 

Hz / RPM 

P-27 

Skip Frequency Centre Point 

0.0 

P-01 

0.0 

Hz / RPM 

The Skip Frequency function is used to avoid the TECDrive operating at a certain output frequency, for example at a frequency which 
causes mechanical resonance in a particular machine. Parameter P-27 defines the centre point of the skip frequency band, and is 
used in conjunction with P-26. The TECDrive output frequency will ramp through the defined band at the rates set in P-03 and P-04 
respectively, and will not hold any output frequency within the defined band. If the frequency reference applied to the drive is 
within the band, the TECDrive output frequency will remain at the upper or lower limit of the band. 

P-28 

V/F Characteristic Adjustment Voltage 

P-07 

P-29 

V/F Characteristic Adjustment Frequency 

0.0 

P-09 

0.0 

Hz 

This parameter in conjunction with P-28 sets a frequency point at which the voltage set in P-29 is applied to the motor. Care must be 
taken to avoid overheating and damaging the motor when using this feature. 

P-30 

Start Mode, Automatic Restart, Fire Mode Operation

 

Index 1 : Start Mode & Automatic Restart 

N/A 

N/A 

Edge-r 

Selects whether the drive should start automatically if the enable input is present and latched during power on. Also configures the 
Automatic Restart function. 



: Following Power on or reset, the drive will not start if Digital Input 1 remains closed. The Input must be closed after a 

power on or reset to start the drive. 



: Following a Power On or Reset, the drive will automatically start if Digital Input 1 is closed. 



 To 



: Following a trip, the drive will make up to 5 attempts to restart at 20 second intervals. The numbers of restart 

attempts are counted, and if the drive fails to start on the final attempt, the drive will trip with a fault, and will require the user to 
manually reset the fault. The drive must be powered down to reset the counter

.

 

Index 2 : Fire Mode Input Logic 

Defines the operating logic when a setting of P-15 is used which includes Fire M, e.g. settings 15, 16 & 17. 

0: Normally Closed (NC) Input

. Fire Mode active if input is open.   

1: Normally Open (NO) Input

. Fire Mode active if input is closed 

Index 3 : Fire Mode Input Type 

Defines the input type when a setting of P-15 is used which includes Fire Mode, e.g. settings 15, 16 & 17. 

0: Maintained Input

. The drive will remain in Fire Mode, only as long the fire mode input signal remains (Normally Open or Normally 

Closed operation is supported depending on Index 2 setting). 

1: Momentary Input

. Fire Mode is activated by a momentary signal on the input. Normally Open or Normally Closed operation is 

supported depending on Index 2 setting. The drive will remain in Fire Mode until disabled or powered off.  

P-31 

Keypad Start  Mode Select  

This parameter is active only when operating in Keypad Control Mode (P-12 = 1 or 2) or Modbus Mode (P-12 = 3 or 4). When settings 
0, 1, 4 or 5 are used, the Keypad Start and Stop keys are active, and control terminals 1 and 2 must be linked together. Settings 2, 3, 
6 and7 allow the drive to be started from the control terminals directly, and the keypad Start and Stop keys are ignored. 

0 : Minimum Speed, Keypad Start 
1 : Previous Speed, Keypad Start 
2 : Minimum Speed, Terminal Enable 
3 : Previous Speed, Terminal Enable 
4 : Current Speed, Keypad Start 
5 : Preset Speed 4, Keypad Start 
6 : Current Speed, Terminal Start 
7 : Preset Speed 4, Terminal Start 

P-32 

Index 1 : Duration 

0.0 

25.0 

0.0 

Index 2 : DC Injection Mode 

Index 1: 

Defines the time for which a DC current is injected into the motor. DC Injection current level may be adjusted in P-59. 

Index 2 : 

Configures the DC Injection Function as follows :- 

0: DC Injection on Stop

. DC is injected into the motor at the current level set in P-59 following a stop command, after the output 

frequency has reduced to P-58 for the time set in Index 1.  

Note

 If the drive is in Standby Mode prior to disable, the DC injection is disabled 

1: DC Injection on Start

. DC is injected into the motor at the current level set in P-59 for the time set in Index 1 immediately after 

the drive is enabled, prior to the output frequency ramping up. The output stage remains active during this phase. This can be used 
to ensure the motor is at standstill prior to starting. 

2: DC Injection on Start & Stop

. DC injection applied as both settings 0 and 1 above.

 

Содержание TECDrive TEC -3-120070-101 Series

Страница 1: ...uide Revision 1 20 www tecmotors co uk tecdrive 1 1 Quick Start Up TECDrive User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 22kW 0 5 30HP 110 480V Distributed by TEC Electric Motors www tecm...

Страница 2: ...TECDrive TEC 3 User Guide Revision 1 20 2 www tecmotors co uk tecdrive 1 Quick Start Up Di and Operating Instructions...

Страница 3: ...ions 14 4 9 Motor Thermal overload Protection 15 4 10 EMC Compliant Installation 15 4 11 Optional Brake Resistor 15 5 Operation 16 5 1 Managing the Keypad 16 5 2 Operating Displays 16 5 3 Changing Par...

Страница 4: ...g from transport receipt of delivery installation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installatio...

Страница 5: ...normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the...

Страница 6: ...before connecting the supply 9 5 EMC Filter Disconnect 28 7 Check the supply cable and motor cable for faults or short circuits 8 Route the cables 9 Check that the intended motor is suitable for use...

Страница 7: ...to Stop Connect a potentiometer 5k 10k between terminals 5 6 and 7 as shown o Adjust the potentiometer to vary the speed from P 02 0Hz default to P 01 50 60 Hz default Quick Start IP66 Switched Switc...

Страница 8: ...1 0 75 1 4 3 1 TEC 3 120070 1F1 TEC 3 120070 101 1 5 2 7 1 TEC 3 220070 1F4 TEC 3 220070 104 1 5 2 7 2 TEC 3 220105 1F4 TEC 3 220105 104 2 2 3 10 5 2 N A TEC 3 320153 104 4 0 5 15 3 3 200 240V 10 3Pha...

Страница 9: ...e suitable for use in pollution degree 1 environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingres...

Страница 10: ...section 9 1 The drive must be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should b...

Страница 11: ...nduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On the...

Страница 12: ...d must be connected to system ground Ground impedance must conform to the requirements of national and local industrial safety regulations and or electrical codes The integrity of all ground connectio...

Страница 13: ...mended to be installed in the supply line for drives where any of the following conditions occur o The incoming supply impedance is low or the fault level short circuit current is high o The supply is...

Страница 14: ...STOP Run in Hand 0 4 Run in Hand Speed controlled from the Local POT Run in Auto 0 Speed controlled using Analog input 2 e g from PLC with 4 20mA signal Run in Speed Control STOP Run in PI Control 5 1...

Страница 15: ...ry Supply Cable Type Motor Cable Type Control Cables Maximum Permissible Motor Cable Length C16 Shielded1 Shielded1 5 Shielded4 1M 5M7 C2 Shielded2 Shielded1 5 5M 25M7 C3 Unshielded3 Shielded2 25M 100...

Страница 16: ...nds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings press and hold Up Down and Stop buttons for 2 seconds The display will show Drive is enabled r...

Страница 17: ...from the motor nameplate enables the slip compensation function and the TECDrive display will now show motor speed in RPM All speed related parameters such as Minimum and Maximum Speed Preset Speeds e...

Страница 18: ...ncy 4 32 8 kHz Sets maximum effective switching frequency of the drive If rEd is displayed when the parameter is viewed the switching frequency has been reduced to the level in P00 32 due to excessive...

Страница 19: ...Power On or Reset the drive will automatically start if Digital Input 1 is closed To Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The numbers of restart att...

Страница 20: ...mmunication An suffix means that the drive will coast stop output immediately disabled but will not trip P 37 Access Code Definition 0 9999 101 Defines the access code which must be entered in P 14 to...

Страница 21: ...3 Advanced Parameters Par Description Minimum Maximum Default Units P 51 Motor Control Mode 0 5 0 0 Vector speed control mode 1 V f mode 2 PM motor vector speed control 3 BLDC motor vector speed contr...

Страница 22: ...cess data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of 85 C...

Страница 23: ...T STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which must be Normally Closed When the input opens the drive trips show...

Страница 24: ...ntrol Mode P 12 3 4 7 8 or 9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 14 1 STOP ENABLE PI Speed Re...

Страница 25: ...emperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance P Loss Input Phase Loss Trip SC trp Communications Loss Trip...

Страница 26: ...gh Run Enable Bit 1 Low Decel Ramp 1 P 04 High Decel Ramp 2 P 24 Bit 2 Low No Function High Fault Reset Bit 3 Low No Function High Coast Stop Request 2 R W Modbus Speed reference setpoint 0 5000 Setpo...

Страница 27: ...8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 9 5 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2 2 2 3 12 1 16 17 5 8 8 10 5 50 3 4 5 20...

Страница 28: ...cording to section 4 3 Suitable Power and motor cables should be selected according to the data shown in section 9 2 and the National Electrical Code or other applicable local codes Motor Cable 75 C C...

Страница 29: ...sed over 10 C in order to start the drive 10 Factory Default parameters loaded 11 External trip E trip requested on digital input 3 Normally closed contact has opened for some reason If motor thermist...

Отзывы: