background image

TECDrive TEC-3 User Guide Revision 1.20 

 

www.tecmotors.co.uk/tecdrive 

5

 

 

1

 
Q

u

ick

 Sta
rt

 Up
 

1.

 

Quick Start Up 

1.1.

 

Important Safety Information 

Please read the IMPORTANT SAFETY INFORMATION below, and all Warning and Caution information elsewhere. 

 

Danger: Indicates a risk of electric shock, which, if not 
avoided, could result in damage to the equipment and 
possible injury or death. 

 

Danger: Indicates a potentially hazardous situation 
other than electrical, which if not avoided, could 
result in damage to property. 

 

This variable speed drive product (TECDrive) is intended for professional incorporation into complete equipment or systems as 
part of a fixed installation. If installed incorrectly it may present a safety hazard. The TECDrive uses high voltages and currents, 
carries a high level of stored electrical energy, and is used to control mechanical plant that may cause injury. Close attention is 
required to system design and electrical installation to avoid hazards in either normal operation or in the event of equipment 
malfunction. Only qualified electricians are allowed to install and maintain this product. 
System design, installation, commissioning and maintenance must be carried out only by personnel who have the necessary 
training and experience. They must carefully read this safety information and the instructions in this Guide and follow all 
information regarding transport, storage, installation and use of the TECDrive, including the specified environmental limitations.  
Do not perform any flash test or voltage withstand test on the TECDrive. Any electrical measurements required should be carried 
out with the TECDrive disconnected. 
Electric shock hazard! Disconnect and ISOLATE the TECDrive before attempting any work on it. High voltages are present at the 
terminals and within the drive for up to 10 minutes after disconnection of the electrical supply. Always ensure by using a suitable 
multi-meter that no voltage is present on any drive power terminals prior to commencing any work. 
Where supply to the drive is through a plug and socket connector, do not disconnect until 10 minutes have elapsed after turning 
off the supply. 
Ensure correct earthing connections.  The earth cable must be sufficient to carry the maximum supply fault current which 
normally will be limited by the fuses or MCB. Suitably rated fuses or MCB should be fitted in the mains supply to the drive, 
according to any local legislation or codes. 
Ensure correct earthing connections and cable selection as per defined by local legislation or codes.  The drive may have a 
leakage current of greater than 3.5mA; furthermore the earth cable must be sufficient to carry the maximum supply fault current 
which normally will be limited by the fuses or MCB. Suitably rated fuses or MCB should be fitted in the mains supply to the drive, 
according to any local legislation or codes. 
Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits.  

 

Within the European Union, all machinery in which this product is used must comply with Directive 2006/42/EC, Safety of 
Machinery. In particular, the machine manufacturer is responsible for providing a main switch and ensuring the electrical 
equipment complies with EN60204-1. 
The level of integrity offered by the TECDrive control input functions 

 for example stop/start, forward/reverse and maximum 

speed is not sufficient for use in safety-critical applications without independent channels of protection. All applications where 
malfunction could cause injury or loss of life must be subject to a risk assessment and further protection provided where needed. 
The driven motor can start at power up if the enable input signal is present. 
The STOP function does not remove potentially lethal high voltages. ISOLATE the drive and wait 10 minutes before starting any 
work on it. Never carry out any work on the Drive, Motor or Motor cable whilst the input power is still applied. 
The TECDrive can be programmed to operate the driven motor at speeds above or below the speed achieved when connecting 
the motor directly to the mains supply. Obtain confirmation from the manufacturers of the motor and the driven machine about 
suitability for operation over the intended speed range prior to machine start up. 
Do not activate the automatic fault reset function on any systems whereby this may cause a potentially dangerous situation. 
IP20 drives must be installed in a pollution degree 2 environment, mounted in a cabinet with IP54 or better. 
TECDrives are intended for indoor use only. 
When mounting the drive, ensure that sufficient cooling is provided. Do not carry out drilling operations with the drive in place, 
dust and swarf from drilling may lead to damage. 
The entry of conductive or flammable foreign bodies should be prevented. Flammable material should not be placed close to the 
drive 
Relative humidity must be less than 95% (non-condensing). 
Ensure that the supply voltage, frequency and no. of phases (1 or 3 phase) correspond to the rating of the TECDrive as delivered. 
Never connect the mains power supply to the Output terminals U, V, W. 
Do not install any type of automatic switchgear between the drive and the motor 
Wherever control cabling is close to power cabling, maintain a minimum separation of 100 mm and arrange crossings at 90 
degrees 
Ensure that all terminals are tightened to the appropriate torque setting 
Do not attempt to carry out any repair of the TECDrive. In the case of suspected fault or malfunction, contact your local Invertek 
Drives Sales Partner for further assistance. 

 

 

 

Содержание TECDrive TEC -3-120070-101 Series

Страница 1: ...uide Revision 1 20 www tecmotors co uk tecdrive 1 1 Quick Start Up TECDrive User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 22kW 0 5 30HP 110 480V Distributed by TEC Electric Motors www tecm...

Страница 2: ...TECDrive TEC 3 User Guide Revision 1 20 2 www tecmotors co uk tecdrive 1 Quick Start Up Di and Operating Instructions...

Страница 3: ...ions 14 4 9 Motor Thermal overload Protection 15 4 10 EMC Compliant Installation 15 4 11 Optional Brake Resistor 15 5 Operation 16 5 1 Managing the Keypad 16 5 2 Operating Displays 16 5 3 Changing Par...

Страница 4: ...g from transport receipt of delivery installation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installatio...

Страница 5: ...normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the...

Страница 6: ...before connecting the supply 9 5 EMC Filter Disconnect 28 7 Check the supply cable and motor cable for faults or short circuits 8 Route the cables 9 Check that the intended motor is suitable for use...

Страница 7: ...to Stop Connect a potentiometer 5k 10k between terminals 5 6 and 7 as shown o Adjust the potentiometer to vary the speed from P 02 0Hz default to P 01 50 60 Hz default Quick Start IP66 Switched Switc...

Страница 8: ...1 0 75 1 4 3 1 TEC 3 120070 1F1 TEC 3 120070 101 1 5 2 7 1 TEC 3 220070 1F4 TEC 3 220070 104 1 5 2 7 2 TEC 3 220105 1F4 TEC 3 220105 104 2 2 3 10 5 2 N A TEC 3 320153 104 4 0 5 15 3 3 200 240V 10 3Pha...

Страница 9: ...e suitable for use in pollution degree 1 environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingres...

Страница 10: ...section 9 1 The drive must be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should b...

Страница 11: ...nduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On the...

Страница 12: ...d must be connected to system ground Ground impedance must conform to the requirements of national and local industrial safety regulations and or electrical codes The integrity of all ground connectio...

Страница 13: ...mended to be installed in the supply line for drives where any of the following conditions occur o The incoming supply impedance is low or the fault level short circuit current is high o The supply is...

Страница 14: ...STOP Run in Hand 0 4 Run in Hand Speed controlled from the Local POT Run in Auto 0 Speed controlled using Analog input 2 e g from PLC with 4 20mA signal Run in Speed Control STOP Run in PI Control 5 1...

Страница 15: ...ry Supply Cable Type Motor Cable Type Control Cables Maximum Permissible Motor Cable Length C16 Shielded1 Shielded1 5 Shielded4 1M 5M7 C2 Shielded2 Shielded1 5 5M 25M7 C3 Unshielded3 Shielded2 25M 100...

Страница 16: ...nds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings press and hold Up Down and Stop buttons for 2 seconds The display will show Drive is enabled r...

Страница 17: ...from the motor nameplate enables the slip compensation function and the TECDrive display will now show motor speed in RPM All speed related parameters such as Minimum and Maximum Speed Preset Speeds e...

Страница 18: ...ncy 4 32 8 kHz Sets maximum effective switching frequency of the drive If rEd is displayed when the parameter is viewed the switching frequency has been reduced to the level in P00 32 due to excessive...

Страница 19: ...Power On or Reset the drive will automatically start if Digital Input 1 is closed To Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The numbers of restart att...

Страница 20: ...mmunication An suffix means that the drive will coast stop output immediately disabled but will not trip P 37 Access Code Definition 0 9999 101 Defines the access code which must be entered in P 14 to...

Страница 21: ...3 Advanced Parameters Par Description Minimum Maximum Default Units P 51 Motor Control Mode 0 5 0 0 Vector speed control mode 1 V f mode 2 PM motor vector speed control 3 BLDC motor vector speed contr...

Страница 22: ...cess data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of 85 C...

Страница 23: ...T STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which must be Normally Closed When the input opens the drive trips show...

Страница 24: ...ntrol Mode P 12 3 4 7 8 or 9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 14 1 STOP ENABLE PI Speed Re...

Страница 25: ...emperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance P Loss Input Phase Loss Trip SC trp Communications Loss Trip...

Страница 26: ...gh Run Enable Bit 1 Low Decel Ramp 1 P 04 High Decel Ramp 2 P 24 Bit 2 Low No Function High Fault Reset Bit 3 Low No Function High Coast Stop Request 2 R W Modbus Speed reference setpoint 0 5000 Setpo...

Страница 27: ...8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 9 5 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2 2 2 3 12 1 16 17 5 8 8 10 5 50 3 4 5 20...

Страница 28: ...cording to section 4 3 Suitable Power and motor cables should be selected according to the data shown in section 9 2 and the National Electrical Code or other applicable local codes Motor Cable 75 C C...

Страница 29: ...sed over 10 C in order to start the drive 10 Factory Default parameters loaded 11 External trip E trip requested on digital input 3 Normally closed contact has opened for some reason If motor thermist...

Отзывы: