TECDrive TEC-3 User Guide Revision 1.20 

www.tecmotors.co.uk/tecdrive 

 

 

1

 

Q

u

ick

 Sta

rt

 Up

 

Declaration of Conformity 

TEC Electric Motors hereby states that the TECDrive TEC-3 product range conforms to the relevant safety provisions of the following council 
directives: 
2004/108/EC (EMC) and 2006/95/EC (LVD)     (Valid until 20.04.2016) 
2014/30/EU (EMC) and 2014/35/EU (LVD)      (Valid from 20.04.2016) 
 
Designed and manufacture is in accordance with the following harmonised European standards: 
 

EN 61800-5-1: 2007 

Adjustable speed electrical power drive systems. Safety requirements. Electrical, thermal and energy. 

EN 61800-3: 2004 
/A1 2012 

Adjustable speed electrical power drive systems. EMC requirements and specific test methods 

EN 55011: 2007 

Limits and Methods of measurement of radio disturbance characteristics of industrial, scientific and 
medical (ISM) radio-frequency equipment (EMC) 

EN60529 : 1992 

Specifications for degrees of protection provided by enclosures 

 

Electromagnetic Compatibility 

All TECDrive products are designed with high standards of EMC in mind. All versions suitable for operation on Single Phase 230 volt and Three 
Phase 400 volt supplies and intended for use within the European Union are fitted with an internal EMC filter. This EMC filter is designed to 
reduce the conducted emissions back into the mains supply via the power cables for compliance with the above harmonised European 
standards. 
It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the EMC 
legislation of the country of use, and the relevant category. Within the European Union, equipment into which this product is incorporated 
must comply with the EMC Directive 2004/108/EC. This User Guide provides guidance to ensure that the applicable standards may be achieved. 
 
All rights reserved. No part of this User Guide may be reproduced or transmitted in any form or by any means, electrical or mechanical including 
photocopying, recording or by any information storage or retrieval system without permission in writing from the publisher. 
 

Copyright Invertek Drives Ltd © 2016 

 
All TECDrive units carry a 2 year warranty against manufacturing defects from the date of manufacture. The manufacturer accepts no liability 
for any damage caused during or resulting from transport, receipt of delivery, installation or commissioning. The manufacturer also accepts no 
liability for damage or consequences resulting from inappropriate, negligent or incorrect installation, incorrect adjustment of the operating 
parameters of the drive, incorrect matching of the drive to the motor, incorrect installation, unacceptable dust, moisture, corrosive substances, 
excessive vibration or ambient temperatures outside of the design specification. 
 
The local distributor may offer different terms and conditions at their discretion, and in all cases concerning warranty, the local distributor 
should be contacted first. 
 

This user guide is the “original instructions” document. All non

-English versions are translations 

of the “original instructions”.

 

 
The contents of this User Guide are believed to be correct at the time of printing. In the interest of a commitment to a policy of continuous 
improvement, the manufacturer reserves the right to change the specification of the product or its performance or the contents of the User 
Guide without notice. 
 

This User Guide is for use with version 3.04 Firmware. 
User Guide Revision 1.20 

 
Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to date 
information, the information contained in this User Guide should be used for guidance purposes only and does not form the part of any 
contract. 
 

 

This manual is intended as a guide for proper installation. Invertek Drives Ltd cannot assume responsibility for the compliance 
or the non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated 
equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation. 

 

This TECDrive contains high voltage capacitors that take time to discharge after removal of the main supply. Before working on 
the drive, ensure isolation of the main supply from line inputs. Wait ten (10) minutes for the capacitors to discharge to safe 
voltage levels. Failure to observe this precaution could result in severe bodily injury or loss of life. 

 

Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved 
should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in 
their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. 

 
 

 

Содержание TECDrive TEC -3-120070-101 Series

Страница 1: ...uide Revision 1 20 www tecmotors co uk tecdrive 1 1 Quick Start Up TECDrive User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 22kW 0 5 30HP 110 480V Distributed by TEC Electric Motors www tecm...

Страница 2: ...TECDrive TEC 3 User Guide Revision 1 20 2 www tecmotors co uk tecdrive 1 Quick Start Up Di and Operating Instructions...

Страница 3: ...ions 14 4 9 Motor Thermal overload Protection 15 4 10 EMC Compliant Installation 15 4 11 Optional Brake Resistor 15 5 Operation 16 5 1 Managing the Keypad 16 5 2 Operating Displays 16 5 3 Changing Par...

Страница 4: ...g from transport receipt of delivery installation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installatio...

Страница 5: ...normally will be limited by the fuses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the...

Страница 6: ...before connecting the supply 9 5 EMC Filter Disconnect 28 7 Check the supply cable and motor cable for faults or short circuits 8 Route the cables 9 Check that the intended motor is suitable for use...

Страница 7: ...to Stop Connect a potentiometer 5k 10k between terminals 5 6 and 7 as shown o Adjust the potentiometer to vary the speed from P 02 0Hz default to P 01 50 60 Hz default Quick Start IP66 Switched Switc...

Страница 8: ...1 0 75 1 4 3 1 TEC 3 120070 1F1 TEC 3 120070 101 1 5 2 7 1 TEC 3 220070 1F4 TEC 3 220070 104 1 5 2 7 2 TEC 3 220105 1F4 TEC 3 220105 104 2 2 3 10 5 2 N A TEC 3 320153 104 4 0 5 15 3 3 200 240V 10 3Pha...

Страница 9: ...e suitable for use in pollution degree 1 environments according to IEC 664 1 For pollution degree 2 or higher environments drives should be mounted in a suitable control cabinet with sufficient ingres...

Страница 10: ...section 9 1 The drive must be mounted vertically on a suitable flat surface The minimum mounting clearances as shown in the table below must be observed The mounting site and chosen mountings should b...

Страница 11: ...nduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for installation using rigid conduit system Power Isolator Lock Off On the...

Страница 12: ...d must be connected to system ground Ground impedance must conform to the requirements of national and local industrial safety regulations and or electrical codes The integrity of all ground connectio...

Страница 13: ...mended to be installed in the supply line for drives where any of the following conditions occur o The incoming supply impedance is low or the fault level short circuit current is high o The supply is...

Страница 14: ...STOP Run in Hand 0 4 Run in Hand Speed controlled from the Local POT Run in Auto 0 Speed controlled using Analog input 2 e g from PLC with 4 20mA signal Run in Speed Control STOP Run in PI Control 5 1...

Страница 15: ...ry Supply Cable Type Motor Cable Type Control Cables Maximum Permissible Motor Cable Length C16 Shielded1 Shielded1 5 Shielded4 1M 5M7 C2 Shielded2 Shielded1 5 5M 25M7 C3 Unshielded3 Shielded2 25M 100...

Страница 16: ...nds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings press and hold Up Down and Stop buttons for 2 seconds The display will show Drive is enabled r...

Страница 17: ...from the motor nameplate enables the slip compensation function and the TECDrive display will now show motor speed in RPM All speed related parameters such as Minimum and Maximum Speed Preset Speeds e...

Страница 18: ...ncy 4 32 8 kHz Sets maximum effective switching frequency of the drive If rEd is displayed when the parameter is viewed the switching frequency has been reduced to the level in P00 32 due to excessive...

Страница 19: ...Power On or Reset the drive will automatically start if Digital Input 1 is closed To Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The numbers of restart att...

Страница 20: ...mmunication An suffix means that the drive will coast stop output immediately disabled but will not trip P 37 Access Code Definition 0 9999 101 Defines the access code which must be entered in P 14 to...

Страница 21: ...3 Advanced Parameters Par Description Minimum Maximum Default Units P 51 Motor Control Mode 0 5 0 0 Vector speed control mode 1 V f mode 2 PM motor vector speed control 3 BLDC motor vector speed contr...

Страница 22: ...cess data output outgoing process data TX PDO1 for CANopen PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of 85 C...

Страница 23: ...T STOP P 24 When both inputs are active simultaneously the drive stops using Fast Stop Ramp Time P 24 E TRIP External Trip input which must be Normally Closed When the input opens the drive trips show...

Страница 24: ...ntrol Mode P 12 3 4 7 8 or 9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABLE FB REF Fieldbus Speed Reference Modbus RTU CAN Master Slave defined by P 12 14 1 STOP ENABLE PI Speed Re...

Страница 25: ...emperature U t Drive Under Temperature Th FLt Faulty Thermistor on Heat sink E trip External Trip 4 20 F 4 20mA fault Ph Ib Phase Imbalance P Loss Input Phase Loss Trip SC trp Communications Loss Trip...

Страница 26: ...gh Run Enable Bit 1 Low Decel Ramp 1 P 04 High Decel Ramp 2 P 24 Bit 2 Low No Function High Fault Reset Bit 3 Low No Function High Coast Stop Request 2 R W Modbus Speed reference setpoint 0 5000 Setpo...

Страница 27: ...8 15 3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 9 5 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2 2 2 3 12 1 16 17 5 8 8 10 5 50 3 4 5 20...

Страница 28: ...cording to section 4 3 Suitable Power and motor cables should be selected according to the data shown in section 9 2 and the National Electrical Code or other applicable local codes Motor Cable 75 C C...

Страница 29: ...sed over 10 C in order to start the drive 10 Factory Default parameters loaded 11 External trip E trip requested on digital input 3 Normally closed contact has opened for some reason If motor thermist...

Отзывы: